SPECIFICATIONS
8.1.3 FR-A842 (400V class)
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 440V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time
for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about √2
.
*5
Value for the ND rating
*6
FR-DU08: IP40 (except for the PU connector section)
*7
For the power voltage exceeding 480V, set Pr. 977 "Input voltage mode selection". (For details, refer to the FR-A800 Instruction Manual.)
For ratings of the converter unit (FR-CC2) refer to the FR-CC2 Instruction Manual.
8.1.4 FR-A846 (400V class)
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 440V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time
for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about √2
.
*5
Value for the ND rating
*6
The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and
cables) affects the rated input current.
*7
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input
reactor and cables).
*8
For the power voltage exceeding 480V, set Pr. 977 "Input voltage mode selection". (For details, refer to the Instruction Manual.)
*9
UL Type 12 Enclosure-Suitable for Installation in a Compartment Handling Conditioned Air (Plenum)
*10
For compliance with IP55, remove the protective bushes and install the recommended cable glands.
Model FR-A842-
07700
(315K)
08660
(355K)
09620
(400K)
10940
(450K)
12120
(500K)
Applicable motor capacity
[kW]
*1
SLD 400 450 500 — —
LD 355 400 450 500 —
ND (initial setting) 315 355 400 450 500
HD 280 315 355 400 450
Output
Rated capacity [kVA]
*2
SLD 587 660 733 834 924
LD 521 587 660 733 834
ND (initial setting) 465 521 587 660 733
HD 417 465 521 587 660
Rated current [A]
SLD 770 866 962 1094 1212
LD 683 770 866 962 1094
ND (initial setting) 610 683 770 866 962
HD 547 610 683 770 866
Overload current rating
*3
SLD 110% of rated motor capacity for 60s, 120% of rated motor capacity for 3s (max. surrounding air temperature 40°C)
LD 120% of rated motor capacity for 60s, 150% of rated motor capacity for 3s (max. surrounding air temperature 50°C)
ND (initial setting) 150% of rated motor capacity for 60s, 200% of rated motor capacity for 3s (max. surrounding air temperature 50°C)
HD 200% of rated motor capacity for 60s, 250% of rated motor capacity for 3s (max. surrounding air temperature 50°C)
Rated voltage
*4
Three-phase 380 to 500V
Regenerative braking torque
*5
(when the converter unit
FR-CC2 is used)
Maximum brake
torque
10% torque/continuous
Input power
Control power supply auxiliary input
Single-phase 380 to 500V 50Hz/60Hz
*7
DC power supply voltage 430 to 780VDC
Permissible control power supply auxiliary input
fluctuation
Frequency ±5%, voltage ±10%
Protective structure (IEC 60529)
*6
IP00
Cooling system Forced air cooling
Weight [kg] 163 163 243 243 243
Model FR-A846-
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
Applicable motor capacity
[kW]
*1
LD 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
ND (initial setting) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
Output
Rated capacity [kVA]
*2
LD 1.62.73.75.88.812 18 22 27 33
ND (initial setting) 1.1 1.9 3 4.6 6.9 9.1 13 18 24 29
Rated current [A]
LD
2.1 3.5 4.8 7.6 11.5 16 23 29 35 43
ND (initial setting)
1.5 2.5 4 6 9 12 17 23 31 38
Overload current rating
*3
LD 120% of rated motor capacity for 60s, 150% of rated motor capacity for 3s (max. surrounding air temperature 40°C)
ND (initial setting) 150% of rated motor capacity for 60s, 200% of rated motor capacity for 3s (max. surrounding air temperature 40°C)
Rated voltage
*4
Three-phase 380 to 500V
Regenerative braking
Maximum brake
torque
*5
10% torque/continuous
Power supply
Rated input AC voltage/frequency
Three-phase 380 to 500V 50Hz/60Hz
*8
Permissible AC voltage fluctuation 323 to 550V 50Hz/60Hz
Permissible frequency fluctuation ±5%
Rated input current [A]
*6
LD 2.1 3.5 4.8 7.6 11.5 16 23 29 35 43
ND (initial setting) 1.5 2.5 4 6 9 12 17 23 31 38
Power supply capacity
[kVA]
*7
LD 1.62.73.75.89 1218222733
ND (initial setting) 1.1 1.9 3 4.6 6.9 9 13 18 24 29
Protective structure
*9
IEC 60529
Dust- and water-proof type (IP55)
*10
UL50
UL Type12
*9
Cooling system Self-cooling + internal fan Forced air cooling + internal fan
Weight [kg] 15 15 15 15 16 17 26 26 27 27