Specifications
23
WIRING
3.4 Control circuit terminals
3.4.1 Terminal layout
*1
The terminal functions as the terminal FM for the FM type, and as the terminal CA for the CA type.
3.4.2 Wiring method
Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the
sheath of the wire and apply directly. Insert the blade terminal or the single wire into a socket of the terminal.
(1) Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighbouring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
(2) Insert wires into a blade terminal, then crimp the terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Blade terminals commercially available (as of February 2012)
*2
A blade terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.
*3
Applicable for the terminals A1, B1, C1, A2, B2, and C2 only.
Cable sheath stripping length
Cable gauge (mm²)
Blade terminal model
Manufacturer
Crimping tool
name
With insulation sleeve
Without insulation
sleeve
For UL wire
*2
0.3 AI 0,5-10WH — —
Phoenix Contact
Co., Ltd.
CRIMPFOX 6
0.5 AI 0,5-10WH — AI 0,5-10WH-GB
0.75 AI 0,75-10GY A 0,75-10 AI 0,75-10GY-GB
1 AI 1-10RD A 1-10 AI 1-10RD/1000GB
1.25, 1.5 AI 1,5-10BK A 1,5-10
AI 1,5-10BK/1000GB
*3
0.75 (for two wires) AI-TWIN 2×0,75-10GY — —
Cable gauge (mm²)
Blade terminal product
number
Insulation product
number
Manufacturer
Crimping tool product
number
0.3 to 0.75 BT 0.75-11 VC 0.75 NICHIFU Co.,Ltd. NH 69
RUNAM
2 5 4 1 F/C
∗1
+24
SD SD S1 S2 PC A1 B1 C1 A2 B2 C2SICSo SOC
5 10E 10 SE SE SU IPF OL FU PC RL RM RH RT AU SD SD CSSTP MRS RES STF STR JOG
Recommended cable
gauge:
0.3 to 0.75mm²
10mm
0
t
o
0
.
5
m
m
S
l
e
ev
e
W
i
r
e
Damaged
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires