User`s manual
3-13
ZM-30 (ZM-61E)
Model
Item
Trend graph Control Memory
Memory “n” specified by
each [0 to 15 tab
windows] (“n” exists by
the number of display
counts)
Graph value memory
Memory “n” (specified by
each [0 to 15 tab
windows]) + 1
Control Memory
Only “memory n” specified by No. 0 of graph at ZM-30
(ZM-61E)
(All graph broken lines are controlled by memory “n”)
Graph value memory
Memory “n” (specified by each [0 to 15 tab windows]) + 1
Numeric key mode
[Type: Direct
Command]
Memory “n”:
Clear (bit 15)
The write flag and dis-
played value of numeric
data entry are cleared at
the timing this bit is
turned ON (0 --> 1).
Input mode [Command Memory]: n
Clear (bit 15)
When this bit is turned ON, the write flag is cleared, and
the display of entered data itself is also cleared.
Entry is enabled when data type and the digit number,
etc. are designated after turning OFF the clear bit (bit 15).
Memory “n” = H0084
(DEC/4-digit designation)
Memory “n” = H8084
(Clear: DEC/4-digit designation)
0 5130
0
Memory “n” = H0084 (DEC/4-digit designation) --> Entry of numeric data
Memory “n” = H8084 (Clear and type designation) --> Memory “n” = H0084
0 5130
0
Numeric key mode
[Type: Block Entry]
Memory “n”:
Clear (bit 15)
After the entry of numeric
data using the numeric
keypad, the keys are
completely disabled.
At the leading edge (0
--> 1) of bit 15, the write
flag using the numeric
keypad is cleared and
the keypad disabled state
is canceled.
Input mode [Command Memory]: n
Clear (bit 15)
After the entry of numeric data using the numeric keypad,
entry for the same data item is not allowed. However,
since the clear (CL) key is valid, the numeric keypad is
enabled by pressing the clear key.
In addition, since the [UP] and [DW] keys are always
valid, entry using the numeric keypad is accepted after
moving the cursor to the next data entry objective data
item.
To enter the data for the same data item continuously,
this bit is valid
Entered value
0.0
0.00
0
0
7 8 9
4 5 6
1 2 3 CLR
0 . +/- ENT
5130
All switches are disabled.
(until the clear bit is set ON.)
Entered value
0.0
0.00
0
0
7 8 9
4 5 6
1 2 3 CLR
0 . +/- ENT
5130
Only these keys are valid.
Sampling
(Bit / Data / Trend)
During scrolling in the
sampling data area using
the [Roll Up]/[Roll Down]
/[Plus Block]/[Minus
Block] switch, nothing is
displayed in the display
area.
During scrolling in the sampling data area using the [Roll
Up]/[Roll Down]/[Plus Block]/[Minus Block] switch, the
cursor is displayed and the data currently selected can be
recognized.
Entry of
numeric data
* It is not possible to gain the totally identical control as ZM-30
(ZM-61E).
ZM-
**
(ZM-62E)
3 ZM-61E -> ZM-62E Conversion