Specifications
58
Special installation (Installation under the floor (using the PDM-4001))
3.4.12 Installation under the floor (using the PDM-4001)
• If protective glass or similar material is used, the multi-installation fixture (PDM-4001) shown in the following figure is
very useful.
600 mm or more
Intake
Exhaust
BB
C
C
Protective glass surface
| Looking in the direction of the arrow (see the next page)
If the display is used in the closed space, observe the following conditions in the above environment:
A ≥ 20 mm (clearance between the protective glass and PDP)
B ≥ 100 mm (clearance between the PDP and side wall)
C ≥ 50 mm (clearance between the PDP and side wall)
A + 50 mm
or less
A
60 mm
or less
Exhaust fan
Flow of air from the air conditioner
Intake port
Tempered glass, etc. (permeable)
Multi-installation fixture (PDM-4001)
BB
C
291mm
A + 50 mm
or less
60 mm or
less
Exhaust port
600 mm or more
Floor
Exhaust
C
PC-9800 (56.4Hz)
PC-9800 (70.1Hz)
VIDEO Machintosh (66.7Hz)
VGA (60Hz)
VGA (72.8Hz, 75Hz)
Without exhaust fan 0~30°C 0~30°C Not usable
With exhaust fan 0~35°C 0~35°C 0~35°C
50mm
* When mounting the down converter (PDA-4003), the same working temperature conditions apply.