NUJD445
SIM02E-003C 
4
mark.  If  dirt  build-up  becomes  excessive,  clean  the  glass 
surface with water only. 
INSTALLATION INSTRUCTIONS -PHOTOVOLTAIC MODULES-
1. INSTALLATION 
   Mounting Using Clips:  
The PV modules can be mounted with clips (clamps) as defined in 
the following. Note that the mounting clips should meet the required 
dimensions as defined in the Figure1. Note that the CLIP CENTER 
POSITION  (e)  from  the  module  corner  should  be  located  in  the 
range as specified in the Annex. All clips shall hold the module frame 
completely within their width. Please be aware that the module under 
heavy  load  would  get  serious  deflection  which  could  cause  cell 
cracks  that  affects  power  degradation.  The  PV  module  must  be 
supported on the array system and must overlap the array rail by at 
least 10mm. 
 Mounting Using Frame Bolt Holes:  
The modules may be fastened to a support using the bolt holes in 
the bottom of the frames at any of locations shown in Annex. The 
module should be fastened with four (4) M8 bolts. Recommended 
torque is 12.5 Nm. 
2. ELECTRICAL INSTALLATION INSTRUCTION 
Cable characteristics 
Conductor size: 4.0mm
2
, Cable type: XLPE cable (H1Z2Z2-K) 
Maximum DC voltage: 1.5kV 
Ambient temperature: -40°C to +90°C 
Maximum conductor temperature: 120 °C
PV module configuration (Recommend) 
# Maximum series configuration: please refer to Table 1 
# Maximum parallel configuration: (Parallel connection of 
each string shall be conducted with following two options. 
Any other parallel connections are prohibited.) 
a)  Case  of  using  the  diodes;  1  diode  per  maximum  2 
parallel strings (Connect a diode or more in series for 
every string or every 2 parallel strings for protection of 
PV module from reverse current over load.) 
b) Case of using the fuses; 1 fuse per every string (Connect 
a fuse for every single string for protection of PV module 
from reverse current over load.) 
Connection cables requirement 
The PV module shall be mated to the same connectors; 
Type: C1 (System voltage 1,500V) 
Brand: Solargiga Energy Holdings Limited 
In case connectors will be replaced by qualified personnel 
according the mounting instructions of the manufacturer of 
the new connectors, the guarantees on the module itself, 
will remain valid according the applicable terms. 
3. WARNING 
Keep  all  PV  MODULES  and 
electriacal CONNECTORS  clean & 
dry before installation. 
4. Disposal 
Dispose  PV  modules  properly.  For 
Information  about  the  proper 
disposal,  contact  your  local 
recycling site.
ELECTRICAL OUTPUT AND THERMAL CHARACTERISTICS 
Rated electrical characteristics are within ±10 percent of the indicated values of Voc, Isc and +5/-0 percent of Pmax, under STC 
(standard test conditions) (irradiance of 1000W/m
2
, AM 1.5 spectrum, and a cell temperature of 25°C (77°F)). 
T able-1. E lectrical characteristics (at S T C )
Model
name
Max imum
Power
(Pmax )
Tolerance
Open-Curcuit
Voltage
(Voc)
Short-Circuit
Current
(Isc)
Voltage at point
of max . Power
(Vmpp)
Current at point
of max. Power
(Impp)
Max imum
system voltage
Over-Current
Protection
Class for protection
against elecrical
shock
Maximum series
configuration(*)
NU-JD445 445W +5%/-0% 49.04V 11.55A 41.32V 10.77A 1,500V 20A
Ⅱ
25
* The maximum series number of modules depends on the local conditions. These values are calculated under the condition of Voc at -40 °C.
Under normal conditions, a PV module is likely to experience conditions that produce more current and/or voltage than reported 
at Standard Test Conditions. Accordingly, the values of Isc and Voc marked on this PV module should be multiplied by a factor 
of 1.25 when determining component voltage ratings, conductor capacities, fuse sizes and size of controls connected to the PV 
module output. 
The PV module has been qualified in an environmental temperature range of -40 °C to +40 °C and up to 100% relative humidity 
as well as rain, and the altitude up to 2,000m in accordance with IEC61730. 
Class for protection against electric shock 
This  PV  module  is  classified  as  “Class Ⅱ ”  according  to 
IEC61730.  These  PV  modules  are  intended  for  installation 
where geeral user access and contact to insulated live parts is 
anticipated. 
FIRE RATING 
This PV module is rated as “Fire safety class C” according to 
IEC61730-2:2004 or UL790.
Figure1. Clips (Clamps) requirement 
 1) Clip: Al alloy, 3 mm Min. thickness 
 2) Catch length (50 mm Min.) 
 3) Covering depth (7 mm Min. on the frame) 
 4) Supporting depth (10 mm Min.) 
 5) Frame (applicable to all frame sections) 
 6) Array rail 
 (applicable to parallel or crossed mounting) 