Installation
NOTE
The battery pack must be connected to the inverter via a communication
cable for proper operation.
6. If the inverter has a ground wire, con-
nect it to the ground screw through the
grommet. The screw type is M6.
7. Use 33 to 50 mm
2
cables as the power
cables to connect the battery pack to
the inverter. Connect the power ca-
bles to the terminal block through the
grommets.
a) Remove the terminal cover plate,
which is placed over the terminal
block to protect it.
b) Connect the negative cable to the
left terminal and the positive cable
to the right terminal. Tighten the
hex-socket screws to a torque of 6
N·m.
c) Restore the terminal cover plate.
NOTE
If you have an expansion battery pack to be installed, do not proceed to
the next step but install the expansion battery pack. See Installing the
Expansion Battery Pack on page 22.