Conguration Switches
Thenumberofbatterypacks Value Setting
1 0011
1
2 0010
2
6.1.2 Settingforbatterycelltype
Make sure that the Cell select DIP switch is set to 00
2
.
6.1.3 SettingsforCANbuspins
Make sure that the CAN_H rotary switch is set to 4. This switch
indicates which pin is used for CAN high signal by the inverter.
Make sure that the CAN_L rotary switch is set to 5. This switch
indicates which pin is used for CAN low signal by the inverter.
Make sure that the GND rotary switch is set to 2. This switch
indicateswhich pin is used for ground by the inverter.
Only 1st to 5th pins can be used.
CAN_H CAN_L GND Setting
4 5 2
6.1.4 Settingforterminalresistors
Make sure that the TermRes DIP switch is set to 11
2
.
Bit On O
1 CAN terminal resistor attached CAN terminal resistor unattached