6 CongurationSwitches
The RESU battery pack and RESU Plus have inside DIP switches and rotary switches, which
must be set correctly for proper communication with the inverter.
6.1 ConguringBatterypack
Remove the switch cover by pulling it up to expose the circuit board.
Switchnumber Type Label Default
1 DIP SW select 0000
2
2 DIP Cell select 00
2
3 Rotary CAN_H 4
4 Rotary CAN_L 5
5 Rotary GND 2
6 DIP Term Res 11
2
6.1.1 Settingforcommunicationinterface
Only one battery pack is installed, set the SW select DIP switch to 0011
2
.
Otherwise, if two are installed, set it to 0010
2
. This switch is initially set to
0000
2
.
NOTE
To be more precise, when a RESU battery pack is directly connected to an inverter,
the SW select DIP switch must be set to 0011
2
.