7. Message Description
Type Code Description Measures
WARNING E513 CELL TEMPERATURE
SENSOR 1EA
Occurs above the standard battery
cell temperature.
PROTECTION E514 CELL TEMPERATURE
SENSOR 2EA
Occurs above the standard battery
cell temperature.
[Table 7-7: BMS general events list]
7.2.7 EMS/Communication Events
Type Code Description Measures
WARNING E601 INVERTER
COMMUNICATION
EVENT
Turn off and restart the system.
Reconnect the communication line
between the EMS board and the
DSP board.
WARNING E602 ETHERNET EVENT Disconnect and reconnect the LAN.
Turn off and restart the Router.
Make sure that the DHCP server
function of Router is activated.
Turn off and restart the system.
WARNING E603 ENERGY METER
EVENT
Make sure that the Meter device is
properly selected.
Disconnect and reconnect the D0
cable.
Turn off and restart the system.
WARNING C128 Ethernet Error Make sure that the Ethernet
communication port and wire
connected properly.
[Table 7-8: EMS/communication events list]
7.2.8 Single Fault Events
Type Code Description Measures
WARNING E701 GRID UNDER VOLTAGE
FAULT
The operation mode is terminated
when a power system event occurs.
Restart 1 minute after the electric
power system event is settled.
E702 GRID OVER VOLTAGE
FAULT
The operation mode is terminated
when a power system event occurs.
Restart 1 minute after the electric
power system event is settled.
E703 GRID UNDER
FREQUENCY FAULT
The operation mode is terminated
when a power system event occurs.
Restart 1 minute after the electric
power system event is settled.
United Kingdom (Eng.) 05/2015. Rev1.1 47