9. Problem Confirmation
Type Code Description Measures
WARNING E509 CELL VOLTAGE
IMBALANCE
PROTECTION
When the imbalance of the Cell voltage is
above the limit value.
Returns to normal when the imbalance of
the Cell voltage is below the limit value.
PROTECTION E510 CELL VOLTAGE
IMBALANCE
PROTECTION
When the imbalance of the Cell voltage is
above the limit value.
Returns to normal when the imbalance of
the Cell voltage is below the limit value.
WARNING E511 AFE
INITIALIZATION
AFE initialization failure
Restored to normal mode on AFE
initialization success
PROTECTION E512 AFE
INITIALIZATION
AFE communication failure
WARNING E513 CELL
TEMPERATURE
SENSOR 1EA
Occurs above the standard battery cell
temperature.
PROTECTION E514 CELL
TEMPERATURE
SENSOR 2EA
Occurs above the standard battery cell
temperature.
[Table 9-6: BMS general events list]
9.1.7 EMS/Communication Events
Type Code Description Measures
WARNING E601 INVERTER
COMMUNICATION
EVENT
Turn off and restart the system.
Reconnect the communication line
between the EMS board and the DSP board.
WARNING E602 ETHERNET
EVENT
Disconnect and reconnect the LAN.
Turn off and restart the Router.
Make sure that the DHCP server function of
Router is activated.
Turn off and restart the system.
WARNING E603 ENERGY METER
EVENT
Make sure that the Meter device is properly
selected.
Disconnect and reconnect the D0 cable.
Turn off and restart the system.
WARNING C128 Ethernet Error Make sure that the Ethernet communication
port and wire connected properly.
[Table 9-7: EMS/communication events list]
76 United Kingdom (Eng.) 05/2015. Rev1.1