Installation Manual
Table Of Contents
- Table of Contents
- Table of Tables
- Table of Figures
- 1. About this Manual
- 2. Safety
- 3. Package Removal and Inspection
- 4. Installation
- 5. Electrical Connections
- 5.1 The Overview of Electrical Connection
- 5.2 Opening the Front Case Cover
- 5.3 The Overview of the Connection Area
- 5.4 Battery Installation
- 5.5 Inner Wiring Connection (Power and Signal Wire Connection for BMS)
- 5.6 Closing the Front Case Cover
- 5.7 A Method of Locking the Distribution Box (Board)
- 5.8 An Installation Method of Energy Meter Electrical Connection
- 5.9 A Connecting Method of the DC Line from the PV
- 6. Communication Connection
- 7. Entering Initial Installation Information
- 7.1 Information Input Administrator
- 7.2 System Information input stage
- 7.3 PC Direct Connection and Local Setting Value
- 7.4 Web Page Connection
- 8. Operation Test
- 9. Problem Confirmation
- 10. Maintenance
- 11. Technical Specifications
- 12. Disassembly
- 13. Contact
9. Problem Confirmation
9.1.4 PV General Events (Protection)
Type Code Description Measures
PROTECTION E301 ON SEQUENCE
GRID OFF
PV generation mode is stopped by the
protection event.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
PROTECTION E302 ON SEQUENCE
INV DC LINK
EVENT
PV generation mode is stopped by the
protection event.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
PROTECTION E303 ON SEQUENCE
PV V EVENT
PV generation mode is stopped by the
protection event.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
PROTECTION E304 NORMAL GRID
OFF
PV generation mode is stopped by the
protection event.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
PROTECTION E305 NORMAL INV DC
LINK & PV I
EVENT
PV generation mode is stopped by the
protection event.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
PROTECTION E306 NORMAL PV V
EVENT
PV generation mode is stopped by the
protection event.
Wait until the event message disappears.
After the event message is removed, it
United Kingdom (Eng.) 05/2015. Rev1.1 73