Installation Manual
Table Of Contents
- Table of Contents
- Table of Tables
- Table of Figures
- 1. About this Manual
- 2. Safety
- 3. Package Removal and Inspection
- 4. Installation
- 5. Electrical Connections
- 5.1 The Overview of Electrical Connection
- 5.2 Opening the Front Case Cover
- 5.3 The Overview of the Connection Area
- 5.4 Battery Installation
- 5.5 Inner Wiring Connection (Power and Signal Wire Connection for BMS)
- 5.6 Closing the Front Case Cover
- 5.7 A Method of Locking the Distribution Box (Board)
- 5.8 An Installation Method of Energy Meter Electrical Connection
- 5.9 A Connecting Method of the DC Line from the PV
- 6. Communication Connection
- 7. Entering Initial Installation Information
- 7.1 Information Input Administrator
- 7.2 System Information input stage
- 7.3 PC Direct Connection and Local Setting Value
- 7.4 Web Page Connection
- 8. Operation Test
- 9. Problem Confirmation
- 10. Maintenance
- 11. Technical Specifications
- 12. Disassembly
- 13. Contact
9. Problem Confirmation
Type Code Description Measures
reversion to the normal state.
E006 BATT
CONNECTION
WARNING
When the battery connection is abnormal.
This is the connection warning message,
with no special change in the sequence.
The warning message disappears on
reversion to the normal state.
[Table 9-1: Inverter general events warning list]
9.1.2 INVERTER General Events (Protection)
Type Code Description Measures
PROTECTION E101 GRID RMS OVER
CURRENT
PROTECTION
The product stops the generating process
because a significant PROTECTION event
has occurred.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
E102 DC LINK OVER
VOLTAG E
PROTECTION
The product stops the generating process
because a significant PROTECTION event
has occurred.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
E103 PV STRING1
REVERSE
CONNECTION
PROTECTION
The product stops the generating process
because a significant PROTECTION event
has occurred.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
event.
E104 PV STRING2
REVERSE
CONNECTION
PROTECTION
The product stops the generating process
because a significant PROTECTION event
has occurred.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant
United Kingdom (Eng.) 05/2015. Rev1.1 69