5. Electrical Connections
As shown in the [Table 5-1], the input / output power cables correspond to the AC/ DC input
/ output specifications for this system.
Recommended cables for the 3.6 kWh All in One
Area Insulation Color code
Grid (L,N) 6mm
2
600V or more Black
PE 6mm
2
600V or more Green with yellow lines
PV (+), (-) 6mm
2
700V or more Black
Object Part List
A AC reactor INVERTER
B DC relay INVERTER
C BDC side connector (BATT-A) INVERTER
D Battery side connector (BATT-B) BAT TERY
E FAN2 INVERTER
F PV1 reactor INVERTER
G PV2 reactor INVERTER
H BDC reactor INVERTER
I FAN1 INVERTER
BD 1 Board1 (PN. SJ92-01425A) INVERTER
BD 2 Board2 (PN. SJ92-01467A) INVERTER
BD 3 Board3 (PN. SJ92-01434A) INVERTER
BD 4 Board4 (PN. SJ92-01426A) INVERTER
BD 5 Board5 (PN. SJ92-01427A) INVERTER
BD 6 Board6 (PN. SJ92-01424C) INVERTER
BD_BM Board battery management (PN. SJ92-01405A) BAT TERY
BD_CAP Board CAP (PN. SJ92-01428A) INVERTER
BT_B Battery Tray bottom view BAT TERY
BT_T Battery Tray top view BAT TERY
CP Communication part INVERTER
E_I/O Electrical I/O part INVERTER
[Table 5-1: Component Description]