Installation Manual
Table Of Contents
- Table of Contents
- Table of Tables
- Table of Figures
- 1. About this Manual
- 2. Safety
- 3. Package Removal and Inspection
- 4. Installation
- 5. Electrical Connections
- 5.1 The Overview of Electrical Connection
- 5.2 Opening the Front Case Cover
- 5.3 The Overview of the Connection Area
- 5.4 Battery Installation
- 5.5 Inner Wiring Connection (Power and Signal Wire Connection for BMS)
- 5.6 Closing the Front Case Cover
- 5.7 A Method of Locking the Distribution Box (Board)
- 5.8 An Installation Method of Energy Meter Electrical Connection
- 5.9 A Connecting Method of the DC Line from the PV
- 6. Communication Connection
- 7. Entering Initial Installation Information
- 7.1 Information Input Administrator
- 7.2 System Information input stage
- 7.3 PC Direct Connection and Local Setting Value
- 7.4 Web Page Connection
- 8. Operation Test
- 9. Problem Confirmation
- 10. Maintenance
- 11. Technical Specifications
- 12. Disassembly
- 13. Contact
2. Safety
2.3.1 Basic Specifications
Item 3600-UK 4600-UK
PV Data (DC)
Max. input total power 6.6 kWp
Max. input power per string 3.3 kWp
Max. input voltage 550 V
Min. input voltage/Initial input voltage 125 V/150 V
MPPT voltage range 125 V~500 V
Max. input current per string 15 A
Number of independent MPPT trackers 2
Battery Data (DC)
Battery capacity 3.6 kWh
Battery voltage range/nominal voltage 48.0 V~65.9 V/60 V
Battery Max. current 46.3 A
Battery nominal current 33.3 A
Discharge of depth 90% (6000 cycles)
Nominal DC/DC power 2.0 kW
DC/DC converter technology Isolated
Grid Data (AC)
Rated power (at 230V, 50 Hz) 3.6kW(*) 4.6 kW(*)
Max. apparent power 5 kVA
Nominal voltage/range 230 V/184 V~264 V
Rated power frequency/range 50 Hz/47.5 Hz~51.5 Hz
Max. current 16A 20A
Max. allowed current for fuse protection 32 A
(*): It can be set 3600W or 4600W by software when installing.
[Table 2-2: Basic Specifications]
2.3.2 Grounding the PV Inverter
The PV inverter complies with the local requirements for grounding the PV inverter.
Samsung SDI recommends connecting and grounding the PV inverter
’s frame and other
electricity conducting surfaces in such a way that there is continuous conduction in order to
achieve maximum protection for systems and persons. And the PV inverter
’s DC (+) pole
and DC (-) pole are not permitted to be grounded.