Operating Manual

Transport
Version 1.1 Page 34 of 92
If you have queries regarding packing and transport safeguarding, please consult BMZ GmbH.
Contact
Telephone: 0049 (0)6188 99 56 9830
Email: CS.BigPack@bmz-gmbh.de
Intermediate storage
The freight packing of the battery, spare parts and replacement parts are designed for a storage duration of a
maximum of 6 months from the delivery.
Storage conditions:
Closed and dry room with a room temperature from +10 °C to +30 °C (temperatures below and above
this range shorten the service life)
Relative air humidity must be a maximum of 80% (non-condensing).
The spatial distance from walls or other objects must be at least 50 cm.
The battery storage system must be stored only in an upright position.
Never clean the battery storage system or its immediate vicinity using a vapour jet or spray water. Dirt and
water may enter the battery storage system and cause major damage.
Before storing the lithium ion battery, inform your insurer.
After a storage time of a maximum of 6 months, execute an equalisation charge process for the battery as described
in the operating manual of the battery inverter.
- If this is not done, batteries may get damaged.
- If this is not done, it will lead to consequential costs which will not be borne by BMZ.
The entire time of storage of batteries must be included in the usage duration.
Transport to the installation site (of the customer)
Only the experts may carry out the transport in accordance with local conditions.
The commercial installer is authorised to transport an energy storage unit without the ADR note for the
transport of hazardous goods.
The free limit for such “transports of hazardous goods” is 333 kg or 999 points (net weight of the
hazardous product x 3 = points /ADR regulation). According to ADR, the identification of the vehicle is
essential from 1000 points onwards ad the driver must have an ADR note.
Every transport must be provided with an accompanying document (transport document as per ADR
hazardous goods UN3480) irrespective of the points.
The transport units are transported on pallets and exclusively in original packages up to the customer’s installation site.
The product must be installed out of the reach of children and animals.