User`s manual

6-8
4. Wiring with power line
Do not run the input signal, output signal and communication cables of the JW300 near and in
parallel with the power line.
- When input and output signal cables are extended over 100 m, make separate wiring for the
input signal and the output signal of JW300.
- Make separate wiring for the input signal and the output signal of the JW300 from the power
line. Particularly with the power line for the inverter and the servo driver, do not place signal
wires inside the same duct or pipe with the power line, even if they are less than 100 m.
PLC
Input
Output
When longer than 100m
Separate wiring
Input
Output
PLC
PLC
Inverter
In the same duct
In separate duct
Inverter