4-2 Power supply module
The power supply modules that can be used with the JW300 are as follows:
*1: The JW-33PU power supply module for theJW20H/30H can also be used with the JW300.
*2: The JW-21PU power supply module for theJW20H/30H can also be used with the JW300.
- When a power supply module is installed on an expansion rack panel, and if a power is supplied to
the power supply module on the basic rack panel without supplying power to the power supply
module on the expansion rack panel, the system detects as "input/output error" (#0160 = Error code
40) or "expansion power supply error" (#0160 = Error code 43). Make sure to supply power also to
the power supply module on the expansion rack panel.
- The power terminal block is equipped with a terminal block cover at delivery. Remove this cover
when you wire. After connecting, make sure to put the cover to the original position.
[1] JW-301PU/31PU/22PU
- The JW-301PU, 31PU, and 22PU are identical in shape.
POWER
RUN
Module name
indication label
Programmer retention
screw hole
Power supply terminal
block (with cover)
=>
See next page
RUN lamp (green)
- Operating normally, lights ON
- Programming after connecting support tool: Blinking (PLC
stops operation)
- Detect errors by self-diagnosis function: Lights OFF (when
battery is error, lights ON.)
Module
retention rib
Rating plate
Module retention
screw
POWER lamp (green)
(Lights when power
is supplied)
ledoM
eman
noitacificepS
devorppA
LU
devorppA
CSA
A5.4CDV5:yticapacrewoP.CAV462ot58
462ot58
A5.3CDV5:yticapacrewoP.CAV
A5.3CDV5:yticapacrewoP.CAV231ot58O
A5.3CDV5:yticapacrewoP.CDV20.4 to 32
O
JW-301PU
JW-303PU
JW-31PU
JW-22PU
*1
*2