User`s manual
9-19
(2) JW-262S
* When the load power source is 5/12 VDC, the load current per point decreases.
Front viewDC output module (sink output) : JW-262S
64 points (Allocation of the first half 64 points of the relay for special module.)
I/O relay : 16 points (dummy)
Relay for special module: 128 points
5/12/24 VDC
4.75 to 26.4 VDC
0.1 A/point, 2 A/common *
0.15 A (100 ms)
0.2 mA or less
1.2 V or less (0.1A)
OFF to ON : 0.5 ms or less
ON to OFF : 1 ms or less (with 0.1A resistance load)
300 mA max. (At all points ON for output.)
Zener diode
Built-in 2.5A fuse (unable replacement). Melt-down
detection function is provided. (When melted down or
external power source is turned OFF, the LED lights.)
Indicator lamps at ON condition (The simultaneous indication
is 32 points max., first half 32 points and second half 32 points
are changed over by the indication changeover switch.)
5/12/24 V (200 mA max.) Use same source with load source
Applicable wire size using connection connector
(accessories) : AWG23 to 26 (0.26 to 0.12 mm
2
)
1000 VAC for 1 minute (between input terminal and secondary circuit)
500 VDC, 10M ohm or more (between input terminal and secondary circuit)
By photo-coupler
1 common line for 32 points (slot common)
Approx. 220g
40 P connector (soldering) x 2
Model name
No. of output
Number of I/O
occupied points
Rated load voltage
Load voltage range
Rated max. load current
Allowable surge current
Min. load current
OFF leak current
ON voltage drop
Response time
(module alone)
Internal current
consumption (5 VDC)
Surge killer
Rated capacity
of fuse element
Operation
indication
External energizer
External wire
connection system
Dielectrical strength
Insulation resistance
Insulation system
Common system
Weight
Circuit diagram
Accessories
Photo-
couple
2.5A
+
—
7
A
B
C
D
Load
L
∼
0
7
∼
0
7
∼
0
7
∼
0
COM1.ABCD(—)
First half 32 points
(Connector CN1 for output)
(+)
Photo-
coupler
2.5A
Fuse
+
—
Load
COM2.ABCD(—)
Second half 32 points
(Connector CN2 for output)
(+)
Fuse???
Internal-circuit
Output
indicator
Power
Supply
Power
Supply
A
B
C
D
7
∼
0
7
∼
0
7
∼
0
7
∼
0
Output
indicator
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Fuse disconnection
checking circuit
See page 4-9 for the pin
No. of connector and
signal name.
A
B
C
D
01234567
JW-262S
2
UNIT
NO.
FUSE
CN2 CN1
1
Rated power
The load current per point
5 VDC
30 mA max.
24 VDC
100 mA max.
12 VDC
60mA max.