User`s manual

9-4
009000 to 009777, 019000 to 019777, ・・・・, 099000 to 099777
E0000 to E0777, E1000 to E1777, ・・・・, E7000 to E7777
109000 to 109777, 119000 to 119777, ・・・・, 199000 to 199777
209000 to 209777, 219000 to 219777, ・・・・, 299000 to 299777
309000 to 309777, 319000 to 319777, ・・・・, 389000 to 389777
Z000 to Z377
Next page
099770 : Second
099771 : Minute
099772 : Hour
099773 : Day
099774 : Month
099775 : Year
099776 : The day of the week
099777 : Control code
JW-311CU
JW-312CU
JW-321CU
JW-322CU
JW-331CU
JW-332CU
JW-341CU
JW-342CU
JW-352CU JW-362CU
Specifications
Items
Timer/counter/MD
Data register
Current timer
storage register
Data memory
- Timer/counter/MD number
00000 to 00777: Timer/counter/MD common
01000 to 17777: Timer/counter common
- Timer set value
100 ms timer (Max. 8192 points : TMR00000 to 17777)
 0.1 sec. to 3276.7 sec.(BIN)
 0.1 sec. to 799.9 sec.(BCD)
10 ms timer (Max. 512 points : TMR 00400 to 00777)*
 0.01 sec. to 327.67 sec.(BIN)
 0.01 sec. to 79.99 sec.(BCD)
1 ms timer (Max. 8 points : TMR 01770 to 01777)*
 0.001 sec. to 32.767 sec.(BIN)
 0.001 sec. to 7.999 sec.(BCD)
* Select units from 10 ms to 100 ms for TMR00400 to 00777, and 
from 1 ms to 100 ms for TMR01770 to 01777 using system memory 
(#0227/#0225). DTMR and UTMR function as 10 ms timers.
- Counter setting value
1 to 32767 (BIN)
1 to 7999 (BCD)
- MD setting value
0 to 999
The current value of the counter and MD are kept ON at power OFF.
Timer is selectable between kept or reset after power OFF. Assignable
timer/counter setting value into registers. (Refer to application
instructions F-260, Fc260, F-261 and Fc261 of JW300 programming
manual.)
1024 points
00000
to 01777
2048 points
00000
to 03777
8192 points
00000 to 17777
24K bytes (kept after power OFF)