9-1 JW300 general specifications
*1 The JW-33PU power supply module for JW20H/30H can be used with the JW300.
*2 The JW-21PU power supply module for JW20H/30H can be used with the JW300.
*3 As for DC input power source, use power source of 20.4 to 32 VDC (ripple rate 20% or less; however,
ripple upper limit: 32 V or less, lower limit: 20.4 V or more).
*4 This value is at max load state of single power supply module.
Chapter 9. Specifications
Items
Power
supply
module
Guaranteed
voltage
interruption time
Power voltage
Storage
temperature
Ambient
temperature
Ambient
humidity
Atmosphere
Dielectrical
strength
Noise immunity
Insulation
resistance
Weight
Vibration
resistance
Shock
resistance
Power
consumption
Grounding
Accessory of
control module
85 to 264 VAC,
47 to 63Hz
Using JW-301PUUsing JW-303PU
85 to 264 VAC,
47 to 63 Hz
Specifications
20.4 to 32.0 VDC *3
85 to 132 VAC,
47 to 63Hz
JW-31PU
(UL/CSA approved)
Available voltage interruption time of 10 ms max.
(Between DC external
terminal and rack panel)
(Between AC external terminal and rack panel)
1000 VAC, 50/60Hz
for 1 minute
(Between DC external
terminal and rack panel)
1500 VAC, 50/60 Hz for 1 minute
(Between AC external terminal and rack panel)
- 20 to 70 °C
0 to 55 °C
35 to 90% RH (Non-condensing)
Free from corrosive gas
When one power supply module, one control module, one memory
module, and eight I/O modules installed in basic rack panel
JIS B 3502 or equivalent
- Multiple vibration width: 0.15 mm (10 to 57 Hz),9.8 m/s
2
(57 to 150 Hz), Number
of sweep: (1 octave/minute), each 2 hours for X, Y, and Z directions
JIS C 0912 or equivalent, 147 m/s
2
(3 times in each X, Y and Z axis)
Class-D grounding
One instruction manual
60 VA max *470 VA max *4
10 M ohm min. at 500 VDC megger
Approx.
3.7 kg
Using JW-22PU
*1 *2
1500 Vp-p 1 µ width impulse
(By noise simulator between the power line and rack panel)