User`s manual

8-5
Clear
System
Monitor
Monitor in HEX
*, * is error code
**
Slot No. (0 to 7)
Rack No. (0 to 3)
Clear
System
Monitor
Monitor in HEX
RS
Contents of
#0160 (HEX)
32, 35
23, 24, 26
25
44
40, 42, 48
60, 70
61, 73
71
72
46, 47
53
22
43
Can’t
monitor in
programmer
Countermeasure
Replace the control module
Under RAM operation: Clear the memory, and then re-load the program. If this
error still occurs, replace the control module.
Under ROM operation: Turn ON the power from OFF. If this error still occurs,
replace the control module.
Program re-loading. If this error still occurs, re-write the ROM program. If this
error still occurs, replace the control module.
Replace the control module. If this error still occurs, replace I/O modules one after
the other from the first module. If this error still occurs, check and replace the
expansion cable and the termination connector. If this error still occurs, replace
the I/O bus expansion adapter. If this error still occurs, replace the rack panel.
Monitor #0046 and replace the I/O module. If this error still occurs, replace the
other I/O modules. If this error still occurs, check and replace the expansion cable
and the termination connector. If this error still occurs, replace the I/O bus
expansion adapter. If this error still occurs, replace the rack panel.
Check the rack No. switches on the expansion rack panel and the I/O bus
expansion adapter (JW-32EA). If this error still occurs, monitor #0046 and replace
the I/O module. If this error still occurs, replace the other I/O modules. If this error
still occurs, check and replace the expansion cable and the termination
connector. If this error still occurs, replace the I/O bus expansion adapter. If this
error still occurs, replace the rack panel.
Check if there are any doubling settings among module No. switches for the
special I/O module, option module, I/O link master module, or device net module.
If this error still occurs, replace the special I/O module, option module, I/O link
master module, and device net module, one after the other.
Check that an I/O module is installed. If this error still occurs, replace the control
module. If this error still occurs, replace the basic rack panel.
Install an I/O module within the max. number of I/O points. If this error still occurs,
replace the control module. If this error still occurs, replace the control module. If
this error still occurs, replace I/O modules one after the other from the first
module. If this error still occurs, check and replace the expansion cable and the
termination connector. If this error still occurs, replace the I/O bus expansion
adapter. If this error still occurs, replace the rack panel.
Monitor #0046 and replace the I/O module. If this error still occurs, replace the
other I/O modules. If this error still occurs, check and replace the expansion cable
and the termination connector. If this error still occurs, replace the I/O bus
expansion adapter. If this error still occurs, replace the rack panel.
Replace the I/O link master module, device net master module (can be monitored
on #0152), and option module (can be monitored on #0150) that FT lamp lights.
Exchange battery. If this error still occurs, replace the control module.
Make sure power is supplied to the expansion power supply. If this error still
occurs, replace the expansion power supply. If this error still occurs, replace the
expansion cable. If this error still occurs, replace the control module. If this error
still occurs, replace the rack panel.
Replace the control module.
[4] Check flow
(1) Check flow 1
Monitor system memory #0160 using a hand-held programmer.
- Monitor operation of system memory #0160
- Monitor operation of system memory #0046