7-55
0000 to 7999 (BCD)
■ CTC (Change setting value of TRM/CNT)
Change timer/counter setting value in the designated program address.
Function
Command
Response
Execution
condition
Example
for use
Communication format
Program
address
Program address
BLOCK No.
BLOCK No.
Program addressBLOCK No.
Setting value
Setting value
Change setting value of address 0000024 to 0100 of PLC01. (Response time: 0 ms)
- 0000 to 0016 [JW-311CU/312CU]
- 0000 to 0032 [JW-321CU/322CU]
- 0000 to 0064 [JW-331CU/332CU]
- 0000 to 0128 [JW-341CU/342CU]
- 0000 to 0256 [JW-352CU]
- 0000 to 0512 [JW-362CU] (Decimal)
- 000000 to 017777 [JW-311CU/312CU]
- 000000 to 037777 [W-321CU/322CU]
- 000000 to 077777 [JW-331CU/332CU]
- 000000 to 177777 [JW-341CU/342CU]
- 000000 to 377777 [JW-352CU]
- 000000 to 777777 [JW-362CU] (Octal)
Stop, does not stop the data written by a HLT command
Write mode Mode 2
Command
Response
A
D
A
D
(H) (L)
R
I
(H) (L)
S
C
S
C
C
R
T
C?
C
BLOCK No.
(4 characters)
Program addresses
(7 characters)
A
D
A
D
(H) (L)
R
I
(H) (L)
S
C
S
C
C
R
T
C?
C
BLOCK No.
(4 characters)
Program addresses
(7 characters)
Setting value
(4 characters)
Station
number
Response
time
Station
number
Response
time
Sum check
code
Sum check
code
01#0CTC000000000245C
01?0CTC0000000002401007F
C
R
C
R
-
-
-
-
-
-
-
-
Note : The MD's setting cannot be changed.