User`s manual

7-32
Turn ON power
COMM port (#0234, #0236, #0266)
PG port (230400 bps)
PG port (19200 bits/sec.)
PG port (115200 bits/sec.)
PG port (9600 bits/sec.)
D5
0
1
Stop bit
1 bit
2 bits
D4
0
0
1
1
Parity
None
Add
Even
D3
0
1
0
1
D2
0
0
0
0
1
D0
0
1
0
1
0
D1
0
0
1
1
0
D7 D6 D5 D4 D3 D2 D1 D0
#0266
Stop bit
Parity Transfer rate
9600
19200
38400
76800
115200
Transfer rate (bps)
D6
0
1
Data length
7 bits
8 bits
Data length
(3) Set EA-PG port (communication port 3)
1) Set system memory #0266
For transfer rate, parity, stop bit, and data length, set ON (1) / OFF (0) of D0 to D6.
2) Set system memory #0267
Set station No., 001 to 037(8).
Remarks
- Change of the communication setting (#0234, #0236, #0266) for the communication ports (PG/
COMM1, PG/COMM2, EA-PG) is effective while turned ON the power.
- However, as the JW300 automatically changes the communication setting as shown below, it will
take few number of retries until establishment of communication after changed settings.
- As shown above, the needs five times of retry to re-establish communication after changed setting,
on the condition that the communication port successfully established communication just before
changing the settings.