User`s manual

7-27
Calculate the value R of the bleeder resistance in the following formula:
V: Power supply voltage
I: Minimum action current of the output module
Then, the capacity of R (W) is
(5) OFF delay time when the DC output module drives the induced load
When the DC output module with a built-in cramp diode is used as a surge killer to drive the
induced load of direct current such as electro-magnetic valves and solenoid valves, it may be
impossible to complete high-speed switching due to the delay of response, since electric current
goes to the load through the cramp diode. In such a case, the DC output module with a built-in
zener diode, instead of the cramp diode, could speed up the response.
DC output module with a built-in zener diode
JW-212SA
(6) When miniature load is driven by a relay output
The relay used in the relay output module is suitable for power drive, and so with a low voltage and
small current such as 24 VDC and 10mA, the contact reliability of the contact point drops. In such
a case, we recommend to use a DC output module (transistor output). When connection with a low
voltage and small current contact point output cannot be avoided, the following connection should
be made: A miniature relay with a reliable contact point under low voltage and small current is
driven, and the contact is made at that contact point.
R<
V
I
W
V
2
R
×3
Margin
Output module
L
Load
DC output module
RY
RY
Connected device
Relay output module
RY
RY
Connected device