User`s manual
3-1
3-1 Basic system configuration
Chapter 3. System configuration
PG/COMM1
PG/COMM2
▲
PULL
電池交換
時期
This
battery
expires
電池の交換
は5分以内
に行ってく
ださい
Exchange
the battery
within
5minutes.
RUN
FLT
CM1
CM2
USB
C
A
R
D
←
F
F
O
SV
PROTECT
INIT
RESET
Expansion rack panel
I/O bus expansion adapter
(JW-32EA)
Terminal connector
(Attached to JW-31EA)
I/O expansion cable
(Total length: max.50m)
I/O bus expansion adapter
(JW-31EA)
Control module
Power supply module
I/O / special I/O module
Basic rack panel
Personal computer, LCD control terminal, etc.
I/O / special I/O / option / device net / I/O link module
Hand-held programmer
JW-15PG
Ladder logic programming
software
Support tool
Computer link
*
*
JW-300SP
(The number of modules
that can be connected:
Maximum 7)
* Note: System can be configured without using an I/O bus expansion adapter. => See the next page.
Number of connectable rack
panels
Number of I/O module,
special I/O module, option
module, Device net module,
and I/O link module to mount
Max. 8 sets in total of 1 basic rack panel and 7 expansion rack panel.
(In case of using the I/O bus expansion adapter JW-31EA/32EA.)
Total of 64 sets can be mounted.
- Max. of 64 I/O modules can be mounted including both the basic
and the expansion rack panels (racks 0 to 7).
- Max. of 64 special I/O modules can be mounted including both the
basic and the expansion rack panels (racks 0 to 7).
- Max. of 8 option modules can be mounted on the basic rack panel.
- A maximum of 4 modules can be installed on a basic rack panel
along with the device net master module (JW-20DN) and an I/O
link master module (JW-23LMH).