User`s manual

DeviceNet (Master) Function
8-19
8
(2) When the JW-32CUM1 is used in the slave mode
Switch settings (slave mode)
Switch name Setting details
Set
value
---
Diagnostic table 39000 to 39377
---
System memory settings, such as free allocation of the diagnostic
table. - See the next page.
SW7
1
Select CU operation status when
an communication error occurs.
*1 ---
2
Select synchronize/asynchronize
between the communication cycle
and CU operation
*2 ---
3
Input/output data allocation
method when editing the scan list
*3 ---
4
5
Data length when editing the scan
list
6
7 Request "explicit" message
8 Basic operation mode Set to ON (slave mode) ON
SW8
- Communication speed (kbps)
- Protected (yes/no)
- Communication monitor time
(long/normal mode) *4
0=125, no, long
1=250, no, long
2=500, no, long
4=125, yes, long
5=250, yes, long
6=500, yes, long
8=125, no, normal
9=250, no, normal
A=500, no, normal
C=125, yes, normal
D=250, yes, normal
E=500, yes, normal
*1: The control section continues operation when a communication error occurs, regardless of
the settings.
*2: Calculations between the communication cycle and the control section will be
"asynchronous", regardless of the settings.
*3: Settings for input/output data allocation are not allowed.
*4: Settings for the communication monitor time are invalid.