User`s manual

DeviceNet (Master) Function
8-10
8
(O: Valid setting —: Invalid setting)
Note: Do not set switch SW8 to "3, 7, B, or F." Otherwise, a malfunction may occur.
11
11
1 Communication speed
Select 125, 250, or 500 kbps.
22
22
2 Protect (yes/no)
Select "Protected" or "Not protected"
- Regardless of protected mode is selected (yes/no) or the JW-32CUM1 (control section) status
(operating/stopped), when a "Bus off" error occurs (F1: Page 8-38), hold down the SCAN
switch for 3 seconds. The JW-32CUM1 will disconnect the network and restart the connection.
(2) Switch SW8
Set the communication speed, protected (yes/no), and the communication monitor time for DeviceNet
communication using the JW-32CUM1.
125
250
500
125
250
500
125
250
500
125
250
500
O
O
Setting for SW8
Communication
speed (kbps)
Protected (yes/no)
Communication
monitor time
0 (Default setting)
1
2
4
5
6
8
9
A
C
D
E
Not protected
Protected
Not protected
Protected
Long mode
Normal mode
Master
Slave
Basic operation
mode
O
O
O
Not protected
When the JW-32CUM1 (control section) is stopped, hold down the SCAN
switch for 3 seconds and it will enter the scan list edit mode.
- The scan list is created by collecting slave data from the slave stations.
- Change the JW-32CUM1 (control section) to operating status and it will start
I/O message operation.
Protected
The SCAN switch will not function.
- This mode is selected to prevent I/O message operation from being stopped
by mistaken operation of the SCAN switch.