User`s manual

Directions for use
7-9
7
Module name Model name
Module
No.
switch
Byte address Flag area
No. of
installation
64 points input JW-264N
Refer to the next page
Max. 28 sets in
one system (one
JW-32CUM1
control module).
Note: Further 8
sets can be
extended by
using remote I/O
slave station.
64 points output JW-262S
Analog input JW-24AD
Analog output JW-22DA
High speed
counter
JW-21HC/22HC
Serial interface JW-21SU
ID control JW-21DU/22DU
Pulse output JW-21PS
Link JW-21CM
SW1
Max. 4 sets only
on JW-34KBM.
SW2
SW3
SW4
SW5
SW6
JW10 link JW-25CM
SW1
SW2
SW3
SW4
SW5
SW6
Net work JW-22CM
The area set by module No. switch differs the
standard function from memory-saving function.
ME-NET JW-21MN
Ethernet JW-255CM ---
FL-net
JW-20FL5
Assign option parameter use area (SW0 to
SW6) using module No. switch setting.
JW-20FLT
I/O link master
station
JW-23LMH SW0
Max. 1 sets only
on JW-34KBM.
(operation mode
7/8 only)
DeviceNet master JW-20DN
Assign I/O data, diagnostic data, and host
Explicit message data using module No. switch
setting.
Max. 3 sets only
on JW-34KBM.
Special I/O module
Option module
I/O
link
Device
Net
1100 to 1177
1200 to 1277
1300 to 1377
1400 to 1477
89000 to 89777
1300 to 1477
59000 to 69757
69000 to 79757
79000 to 89757
89000 to 99757
2000 to 3757
1510 to 1517
1520 to 1527
1530 to 1537
1540 to 1547
1550 to 1557
1560 to 1567
1510 to 1511
1520 to 1527
1530 to 1537
1540 to 1547
1550 to 1557
1560 to 1567
- Set the module No. switch to 0 on option modules or DeviceNet master modules installed on the JW-
34KBM (JW-32CUM1). The JW-32CUM1 communication section uses the "0" data area.
- Special I/O module can only be mounted on racks 0 to 3. (It can not be mounted on racks 4 to 7.)
When using the 64 points I/O module, the number of mountable sets varies with the model of the
control module.
eludomstniop46fotnuomalatoT stniopO/Ifo.oN.xaM
stes61.xaMstniop4201
7-3 Data memory for special I/O, option, I/O link, and DeviceNet
Data memory for special I/O option module is set by module No. switch of module face as follows.
The number of modules that can be installed, as shown below, is correct when a JW-32CUM1 is used as
the control module.
0100 to 0177 1570 to 1571