User`s manual

Connection (Wiring) Method
6-2
6
Miniature flat blade
screwdriver
Cable securing screw
Ground
Blue (CAN L)
White (CAN H)
Black (V
)
Red (V+)
Connector (mounting)
Communication cable
Remarks
From the previous page
6 Insert the signal line, power line, and the ground line into the appropriate connector holes.
- Insert the wires from the top down, in the following order: red, white, ground , blue, and black.
Pay strict attention to the connector orientation.
- Before inserting the wires, loosen the screws on the connector enough to insert the wires easily.
- The JW-32CUM1 is supplied with one set of MSTB2.5/5-STF-5.08AU (With a screw to secure the
connector: Phoenix Contact).
7 Secure each wire tightly using the wire retention screws of the connector.
- Use a miniature flat blade screwdriver which has the same diameter from the neck all the way to the
end. Tighten the screws using 0.5 N-m of force.
When connecting two thin cables in a multi-drop system
Insert the wires from each cable with the same color insulation into the same hole.
- Crimp a terminal to the tip of the two wires.
- Before connecting the communication cable, make sure to turn OFF the power to the JW30H,
all slave stations, and the communication power supply.
- Do not pull hard on the communication cable since the connector can be pulled off or
disconnected easily.