User`s manual
5-1
Installation
5
[1] Installation of the JW-34KBM
Drill M5 tapped installation holes on the control panel wall and secure the JW-34KBM basic rack panel to
the panel wall using M5 screws.
- For installation dimension details regarding the JW-34KBM, see Section 4-2.
- Allow 50 to 150 mm distance between each rack panel. Allow 50 mm or more between the left and right
walls, or a wiring duct. Allow 30 mm or more between a wiring duct above or below the basic and
expansion rack panels. => See Section 6-4.
[2] Installation of the JW-32CUM1
Install the JW-32CUM1 control module at the JW34KBM basic rack panel (the power supply module on
the right.)
1 Set the switches on the back of the JW-32CUM1 (SW2 to 5, 7, and 8).
For details, see "Switch settings" in Chapters 8 to 12.
2 Insert the connector on the JW-32CUM1 into the control module slot on the JW-34KBM.
3 Screw in the module securing screws (2 at the top and 1 at the bottom) for the JW-32CUM1, using
a Philips screwdriver.
Chapter 5: Installation
Control panel
JW-34KBM
Module inserting guide
Module retention rib
Inserting hole of module retention rib
JW-32CUM1
JW-34KBM
JW-32CUM1
Module retention screw
Power supply module
Phillips screwdriver