User`s manual

13-4
Specifications
13
Items Specifications
Data memory
Timer/counter/MD
Register
Current timer
storage register
Total 1024 points (000 to 1777 : common for both timer and counter)
- Timer set time
100 ms timer (TMR0000 to 1777)
0.1 sec. to 199.9 sec.
0.1 sec. to 3276.7 sec. (BIN)
0.1 sec. to 799.9 sec. (BCD)
10 ms timer (TMR 0400 to 0777)
0.01 sec. to 19.99 sec. (BCD)
TMR 0400 to 0777 is selectable timer feature of 100 ms unit and 10 ms
unit.
- Counter setting value 1 to 1999
1 to 32767 (BIN)
1 to 7999 (BCD)
- MD setting value 0 to 999
The current value of the counter and MD are stored at power OFF. The
timer is selectable between kept or reset after power OFF. Assignable
timer/counter setting value into registers. (Refer to application instructions
F-260, Fc260, F-261 and Fc261 of the JW30H programming manual.)
9216 bytes (kept after power OFF)
09000 to 09777, 19000 to 19777, 29000 to 29777,
39000 to 39777, 49000 to 49777, 59000 to 59777,
69000 to 69777, 79000 to 79777, 89000 to 89777,
99000 to 99777, E0000 to E7777.
Second : 99770
Minute : 99771
Hour : 99772
Day : 99773
Month : 99774
Year : 99775
The day of the week : 99776
Control code : 99777