User`s manual
13-2
Specifications
13
13-2 JW30H (JW-32CUM1) system specifications
Shown below are the system specifications when using the JW-32CUM1 as a control module and a
JW-34KBM as the basic rack panel.
*1: When using a JW-31EA/32EA I/O bus expansion adapter.
*2: When using JW-38ZB expansion rack panels (7 modules).
Item Specifications
Number of rack panel
connected
Max. 8 sets in total of 1 basic rack panel (JW-34KBM) and 7
expansion rack panel.*1
Total length of expansion
cable
Max. 50 m *1
Number of I/O points Max. 1024 points
Number of mounting
I/O module, special I/O
module, and option module,
etc.
Total of 60 sets can be mounted *2
- Max. of 60 I/O modules can be mounted including on both the
basic and the expansion rack panels (racks 0 to 7).
- Max. 28 special I/O modules can be mounted including on both the
basic and the expansion rack panels (racks 0 to 3).
- Max. of 4 option modules can be mounted on the basic rack panel.
- Max. of 1 I/O link master module (JW-23LMH) can be
mounted on the basic rack panel. (Operation mode 7/8 only.)
- Max. of 3 DeviceNet master modules (JW-20DN) can be
mounted on the basic rack panel.
Number of I/O relay occupied
points of I/O module, special
I/O module, option module.
(Allocation of relay address)
Option, I/O link and special I/O module is execlusive use relay area
except for I/O relay area.
Program memory
The JW30H has a memory section for storing the user program as
standard. (Fixed capacity).
The program can be stored in the built-in flash ROM.
Module Item
Number of I/O relay
area occupied points
8 points input/output module 16 points
16 points input/output module 16 points
32 points input/output module 32 points
Special I/O module 16 points
Option module 16 points
I/O link master module
DeviceNet master module
16 points
Not installed (Vacant slot) 16 points