User`s manual

11-14
Data link DL9 (master station) function
11
[4] How to make synchronize
In order to securely execute data transfer between a master station (JW-32CUM1) and a slave station, we
recommend to synchronous these stations.
(1) Synchronous with OUT instruction
Master station Slave station 01
1000 to 1002 (
1003 to 1004 (
) コ1000 to 1002
) 1003 to 1004
Sending
Receiving
Sending station program
00000
10000
10030
10000
10000
10030
F-45
Receiving side
- Turn ON 10000 at the sending station. OUT 10000 shall be self latch circuit.
- When 10000 of the receiving station turns ON, it turns ON OUT 10030. Return this signal to the
sending station.
Remarks
As shown in the figure below, module may not able to receive signal of one scanning interval of the
PC.
10000
00000
F-44
(2) n byte transfer
To make synchronous for all the data, add the synchronous signal at the head and the end of data
area.
1200
1203
0200
0203
Synchronous signal Synchronous signal
Data transfer
Synchronous
signal 12000
Synchronous
signal 12030
Synchronous
signal
F00
F00
0201
0400
02020401
F00
F00
0400
0401
1201
1202
00000
02000 02030