User`s manual

10-3
Data link DL1 (master station) function
10
[2] Communication contents of data link DL1
The data link DL1 function is available to communicate the data memory contents of a PC through data
link area.
When the master station (JW-32CUM1), slave station 01 and a slave station 02 each send 16
bytes of data:
- Master station data link area: 1000 to 1077 (Fixed areas in the JW-32CUM1)
- Slave station 01 data link area: 0200 to 0277
- Slave station 02 data link area: 0200 to 0277
Master station
(JW30H: JW-32CUM1)
Slave station 01 (JW20H)
Slave station 02 (JW50H)
1000
1020
1040
0200
0220
0240
0200
0220
0240
: means sending
: means receiving
Master station program Slave station 01 program Slave station 02 program
12000
12001
12002
12006
12007
2001
2002
2006
2007
2000
2001
2002
2006
2007
2000
2200
2200
2401
12200
12401
2401
Remarks
- You cannot specify a specific station to receive data. All of the stations will receive the same data
from any other station.
- Write the link relay of the sending station as an OUT instruction in PC program. The link relay of
the sending station is usable as a D (destination) side of the application instruction.
- Write the link relay of the receiving station as an input signal in PC program. The link relay is
usable as the S (source) side of the application instruction.
- Sending data and receiving data correspond to 1 point unit bit.
76543210
1000
76543210
1020
76543210
0200
76543210
0220
Becomes the same value as 0220
slave station.
Becomes the same value as 1000
master station.