User`s manual
Remote I/O (master station) function
9-14
9
[3] Error code
When an error occurs in remote I/O operation, the error code is stored in system memory location #170 in
the JW-32CUM1. For details about responding to errors, see page 9-18.
(1) Errors on master and slave stations
Errors on master station (JW-32CUM1)
Error code
Contents
80
(H)
81(H)
82(H)
83(H)
84(H)
88(H)
89(H)
8A(H)
8B(H)
8C(H)
8D(H)
Master station setting error
- Check the switch settings in the JW-32CUM1.
Error at communication with slave station 1.
Error at communication with slave station 2.
Error at communication with slave station 3.
Error at communication with slave station 4.
Table verify error of a slave station.
Slave station 1 I/O error.
Slave station 2 I/O error.
Slave station 3 I/O error.
Slave station 4 I/O error.
Special I/O Module switch setting error of slave station.
Remarks
- The error code stored in the system memory #170 shifts from #170 to #177 one by one each new
error code occurrence, and stores the error conditions up to 8 causes. When the JW30H is in
RAM operation, the error code memory does not disappear even if the power to the JW30H is
turned off. The system memory #170 to 177 keeps its contents after recovering from the error
condition.
- When the JW-32CUM1 (general purpose communication section) becomes error, it stores error
code "53" (option error) in the system memory #160.
- In the case of an option error "53
(H)
," when you monitor system memory #050, the bit (module No.
swith setting value) of error option module switches ON. When more than 1 bit is error, these bits
switch ON. The each ON bit becomes OFF by recovering from the error condition. But the last ON
bit does not become OFF even if the error condition recovers.
Error of slave station 1.
Error of slave station 3.
#177 #176 #175 #174 #173 #172 #171 #170
81
81 83
Delete
#050
76543210
Module error
of module
switch No.5
Module error
of module
switch No.3
Module error
of module
switch No.1
Module error
of module
switch No.4
Module error
of module
switch No.2
Module error
*
of module
switch No.0
* When an error occurs in the JW-32CUM1 (general purpose