Specifications
25
Checking Output Power
The output power of the last 7 days (the current day is included) can be checked.
Press "ENT" and "SEL" in the front panel for the operation.
Setting item Setting code Parameter
Utility over-voltage parameter (V) 1 250 255 260 ---
Utility under-voltage parameter (V) 2 205 210 215 ---
Over-voltage /Under-voltage settling time (Sec) 3 1.0 1.4 1.8 ---
Utility frequency over parameter (Hz) 4 52 53 54 ---
Utility frequency under parameter (Hz) 5 46 47 48 ---
Utility frequency over/under settling time (Sec) 6 1.0 1.4 1.8 ---
Protection timer (Sec) 7 10 60 150 300
Option
*This setting is not used. Do not change the
parameter (Leave the value as default of "5").
85
One thing
at a time
31 ---
Operating frequency (Sec) 9 50 60 --- ---
Press "ENT" for 5 seconds.
Normal
operation
ENTSEL
ENTSEL
Press "SEL".
ENTSEL
Press "SEL".
ENTSEL
The output power goes back one day as "SEL" is pressed.
The display returns to the current day by pressing "SEL"
after output power of 6 days ago is displayed.
ENTSEL
Press "ENT". The output power of the day is displayed.
After checking is finished, press "ENT" to display "dAY-P". Then switch displays until "OFF" is displayed.
After "OFF" is displayed, press "ENT" for 5 seconds.
Press "ENT" for
5 seconds.
ENT