Technical data
6
©
FuG Elektronik GmbH, D-83135 Schechen, Am Eschengrund 11
http://www.fug-elektronik.de, E-Mail: info@fug-elektronik.de
V 0913
Low voltage power supplies double stabilized
Series NTN from 6,5 V to 350 V / 35 W to 100 kW
NTN 700 - 125
125V / 5A
Design Example
Features:
Simple construction
Short circuit proof and unlim-
ited operation with full current
in short circuit condition
Voltage and current regulation
with automatic and sharp
transition; control modes
indicated by LEDs
Voltage and current setting
via 10-turn potentiometers
with precision scale; the ad-
justing knob can be locked
4½ digit DVM for voltage and
current (for table-top models)
Sense terminals for the com-
pensation of voltage drop on
the load lines. The nominal
voltage always refers to the
output terminals
Parallel and series connection
possible
Suitable also for inductive and
capacitive loads
Safety interlock loop and
internal interlock is standard
on three-phase units
Elapsed-hour meter as a
standard on three-phase units
Function:
The mains voltage is transfor-
med to the appropriate level. On
the secondary side of the trans-
former is a thyristor controlled
rectifier stage (phase cutting
circuit), the output of which is
used to charge a capacitor
bank. This capacitor bank is
also connected to the final se-
ries regulating transistor output
stage. By controlling the con-
duction angle of the thyristors
after each zero-crossing of the
sinusoidal voltage, the flow of
energy is regulated in such a
way as to have a defined volt-
age drop across the final series
transistor stage (pre-regulation).
The performance of the final
series transistor stage defines
the final stability of the output
voltage (main regulation).
Design:
Up to 140W nominal power
½19" table-top case
For 350W nominal power or
higher 19" table-top case
19" Rack-adapters for mount-
ing into a 19" rack are availa-
ble as accessory
For 7kW nominal power or
higher 19" cabinet. Height
depending on type. The side
covers are detachable and the
rear door is lockable.
All cabinets are equipped with
fork-lift-compatible plinths and
removable crane-eyes.
Single cabinets up to 38U are
easily transportable by fork-
lift.
Cooling is carried out via
convection or built-in fans,
with the air being exhausted
(depending upon type) either
via the rear or the top. For
high power units water cool-
ing can also be used.
Output:
Output isolation:
The output is floating, maxi-
mum operating voltage with
respect to earth: ±500V. Ei-
ther the positive or the nega-
tive terminal may be connect-
ed to earth. For units
equipped with the analog
programming: the "0V" of the
analog programming is con-
nected to the positive output.
Output terminals:
Up to 20A output current,
4mm safety connectors are
used on the rear side. For
currents up to 300A - clamps
are fitted whilst for higher
currents we use copper bars.
Technical Data:
Mains connection:
Up to 1400W nominal power:
230V ±10% 47Hz to 53Hz
For 2800W and higher:
400V ±10% 47Hz to 53Hz;
two-phase
For 7000W and higher:
400V ±10% 47Hz to 53Hz;
three-phase
Ambient temperature: 0°C to
+40°C
The following data applies for
voltage and current regulation,
and refers to the rated value
(unless otherwise stated):
(For explanations please refer
to Definitions and Terms on
page 54.)
Setting range:
from approx. 0,1% to 100%
Setting resolution:
±1 x 10
-4
Residual ripple (0 - 10MHz):
<1 x 10
-4
pp + 10mVpp
Recovery time:
Voltage control:
<50µs for load changes from
10% to 100% or from 100% to
10%.
Current control:
<500ms for load changes
causing an output change of
less than 10% of the rated
voltage.
Units with output voltage
>65V, will switch off for a
short time at high and fast
load changes.
Setting time at nominal load:
100ms to 500ms for changes
of the output voltage from
10% to 90% or 90% to 10%
Discharge time constant for
output without load:
approx. 2sec. to 60sec., de-
pending on type
Deviation:
For ±10% mains voltage vari-
ation:
<± 1 x 10
-5
For no load / full load:
<2 x 10
-4
Over 8 hours under constant
conditions:
<±1 x 10
-4
Within the temperature range:
<±1 x 10
-4
/K
Possible Options:
Coarse/fine-potentiometers
(99% / 1%) for more accurate
adjustment of voltage and / or
current
Analog programming (The
positive output has to be
earthed; see also page 44)
Analog programming, floating
(see page 44)
Computer interfaces - IEEE
488, RS 232, RS 422, Profi-
bus DP, USB, LAN (more on
request) (see page 46)
Roller blades for cabinet units
Higher stability (see page 48)
Power limitation (see page
48)
More options and special solu-
tions on request. Some options
may involve changes to the
description of the unit - espe-
cially concerning the mechani-
cal design.