Technical data

49
©
FuG Elektronik GmbH, D-83135 Schechen, Am Eschengrund 11
http://www.fug-elektronik.de, E-Mail: info@fug-elektronik.de
V 0913
Accessories:
Isolating transformers
Function:
High voltage isolating trans-
formers are used to provide
mains supply to loads located
on a high voltage potential. The
primary winding is earthy.
Features:
Compact size
Moulded in artificial resin
Low capacity
Double screened
Technical data:
Input voltage:
230V 47 - 63Hz
Output voltage:
230V 47 - 63Hz
Isolation:
primary / secondary: 50kV
DC
Test voltage:
75kV DC for 1 min.
Test voltage between primary
winding, primary screen and
core: 7.5kV DC
Test voltage between sec-
ondary winding and second-
ary screen: 7,5kV DC
Design:
Mechanical design:
Core and windings are com-
pletely moulded in artificial
resin with isolating cross-
pieces between the connec-
tions. Attachment at the bot-
tom with 4 x M8 female
thread.
Connections:
Primary and secondary side
by threaded bolts, M6, to top,
screen connections on free
wire endings.
Special designs:
Different voltages
Different isolation voltages
Higher power
Three phase versions (see
picture above)
Design examples HTS 200 - 50 HTS 3000 - 50 3p
Three phase version
HTS 100 - 50 100 VA 165 mm 220 mm 160 mm 15 kg
HTS 500 - 50 500 VA 210 mm 230 mm 200 mm 21 kg
HTS 1000 - 50 1000 VA 210 mm 200 mm 200 mm 25 kg
HTS 2000 - 50 2000 VA 252 mm 260 mm 252 mm 40 kg
HTS 3000 - 50 3000 VA 252 mm 270 mm 250 mm 43 kg
Hight
Depth
Weight
Ty pe
Nominal pow er
Width