Technical data

47
©
FuG Elektronik GmbH, D-83135 Schechen, Am Eschengrund 11
http://www.fug-elektronik.de, E-Mail: info@fug-elektronik.de
V 0913
Options and modifications:
Probus V (digital interface system)
RS 422:
Baud rates up to 625kBd pos-
sible.
Optical connectors: Standard
Agilent (HP) HFBR-0500
series. Optionally HFBR-0400
series.
USB:
Control via virtual COM-Port
or directly via USB-driver.
(Virtual Com-Port driver for
the most common operation
systems available, very sim-
ple programming, no USB-
programming knowledge ne-
cessary.)
Delay time typical approx.1ms
due to USB principle.
Possible analog and digital interface alternatives for
FuG - Power supplies (Overview)
LAN (Ethernet):
Control via virtual COM-Port
or directly by TCP/IP-
programming.
(Virtual Com-Port driver for
the most common operation
systems available, very sim-
ple programming, no pro-
found knowledge of TCP/IP-
programming necessary.)
Delay time approx. 20ms.
.
Profibus DP:
An initial data block is made
available on the Profibus-DP
side. Into this the primary SPS
writes the required set points
and control commands.
This initial data block is trans-
ferred cyclically by the con-
verter via optical link to the
ADDA part.
The feedback data (e.g.
measurements) of the ADDA
part is questioned cyclically
and provided n the exit data
block of the converter to the
primary SPS.
Cycle time 40ms.
Profibus address selectable
by code-switch outside the
unit.
Mode indication for Profibus
connection (red Error-LED).
Mode indication for optical
link.
The Profibus-DP interface
does not support the intercon-
nection of several ADDA
modules