NUJD440
SIM02E-003A 
3 
4. SITE SELECTION 
In most applications, the PV modules should be installed in a 
location where there is no shading throughout the year. In the 
Northern Hemisphere, the PV modules should typically face  
south, and in the Southern Hemisphere, the PV modules should 
typically face north. 
Please  make  sure  that  there  are  no  obstructions  in  the 
surroundings of the site of installation. TAKE PROPER STEPS 
in  order  to  maintain  reliability  and  safety,  in  case  the  PV 
modules  are  used  in  areas  such  as:  Heavy  snow  areas  / 
Extremely cold areas / Strong wind areas / Installations over, or 
near, water / Areas where installations are prone to salt water 
damage/corrosive  gas  environment/  Small  islands  or  desert 
areas. 
The results of the ammonia test and the salt-mist-corrosion test 
on the PV modules, carried out under such strict test conditions, 
should be disclosed for reference purposes only. The decision 
on  whether  the  PV  modules  are suitable  and  compatible  for 
each installation field will depend on the user’s judgement and 
responsibility. 
5. TILT ANGLE 
The tilt angle is the measurement between the PV module and 
a  horizontal  ground  surface.  The  PV  module  generates  the 
maximum output power when it faces the sun directly. 
5 degrees or more is recommended for the tilt angle of the PV 
module for the maintenance (See 9. Maintenance). 
For  the  standalone  systems  with  a  battery  where  the  PV 
modules are attached to a permanent structure, the tilt angle of 
the  PV  modules  should  be  determined  to  optimize  the 
performance when the sunlight is the scarcest. In general, if the 
electric power generation is adequate when the sunlight is the 
scarcest, then the angle chosen should be adequate during the 
rest of the year. For grid-connected installations where the PV 
modules  are  attached  to  a  permanent  structure,  it  is 
recommended to tilt the PV  module at the angle equal to the 
latitude of the installation site so that the power generation from  
the PV module will be optimum throughout the year. 
6. WIRING 
To  ensure  proper  system  operation  and  to  maintain  your 
guaranty, observe the correct cable connection polarity (Figures 
1 & 2) when connecting the PV modules to a battery or to other 
PV modules. If not connected correctly, the bypass diodes could 
be destroyed. 
PV  modules  can  be  wired  in  series  to  increase  voltage. 
Connect wires from the positive terminal of one PV module to 
the negative terminal of the next PV module. Figure 1 shows PV 
modules connected in series. 
Connect PV modules in parallel to increase current. Connect 
wires from the positive terminal of one PV module to the positive 
terminal on the next PV module. Figure 2 shows PV modules 
connected in parallel. 
7. GROUNDING 
The frame grounding must consider the local requirement and 
regulation at the installation site. When grounding is required, 
please refer to below example connection (Figure 3).  Please 
be careful in arranging the system ground so that the removal 
of one PV module from the circuit will not interrupt the grounding 
of any other PV modules. 
The PV modules should be grounded to the same electrical 
point as described below. 
You  can  use  a  hole  with  the  appropriate  symbol  for 
equipotential bonding on the side frame for either a bolt, nut and 
washer grounding the PV module  to the frame, a ground lug 
fastened by bolt or screw, or appropriate screw (hardware not 
provided). An example of acceptable ground connection using 
a bolt, nut and washer retaining a ground lug is shown in Figure 
3. In a connection of this type, the hardware (such as a toothed 
locked washer / star washer) must score the frame surface to 
make electrical contact with the frame. The ground wire must 
be  considered  within  the  local  requirement  of  local  and 
regulation at the site of installation. 
8. MOUNTING 
Please  make  sure  that  all  the  information  described  in  the 
INSTALLATION  MANUAL  is  still  valid  and  proper  for  your 
installation. The mounting method has been verified by SHARP 
and NOT CERTIFIED by a third party organization. 
The approved way to mount SHARP PV modules to a support 
structure is described in this INSTALLATION MANUAL. 
Although SHARP does not specify or warrant frame  clips or 
clamps,  using  frame  clips  (not  provided)  or  clamps  (not 
provided) is possible when they are designed for PV modules 
and with minimum dimensions on the sides of the PV module in 
accordance with the instructions and drawings provided. If using 
frame clips or clamps, the PV modules should be fixed rigidly 
and there shall be no damage to the PV modules by deforming 
mounting structure against design load. 
The SHARP PV module guaranty may be void  if customer-
selected frame clips are improper or inadequate for PV module 
properties (including strength or material) or installation. Note 
that if metal clips are used, there must be a path to ground from 
the clips, (for instance, using star washers in the clip hardware 
set).Please review the descriptions and drawings carefully; not 
mounting the PV modules according to one of these methods 
may void your guaranty. The PV module has passed the test 
sequence which contains 3 cycles each performed at 5,400 Pa 
positive  and  2,400  Pa  negative  loading  in  accordance  with 
IEC61215-2.  The  system  designer  shall  be  responsible  to 
ensure protective structures so that the module can bear to the 
loads that are different from the test condition defined in the IEC 
standard. 
 Support structures that PV modules are mounted on should 
be rigid. SHARP PV modules are designed to ensure optimal 
electrical  performance  under  the  condition  that  they  are 
mounted  on  rigid  support  structures.  Deformation  of  support 
structure may damage PV module with its electric performance. 
When mounting the PV module on structure, ensure that no 
corner has a displacement of more than 2 mm per every 
1000 mm of the diagonal. The mounting structure shall enable 
the PV module to deflect freely under wind and/or snow load not 
to make direct impact to the center of the PV module 
(i.e. min. 10 cm from the roof surface to the bottom face of PV 
module  frame).  The  installer  shall  be  responsible  for  the 
selection and construction of support structure. 
9. MAINTENANCE 
The PV modules are designed for long  life and  require very 
little maintenance. If the angle of the PV module is 5 degrees or 
more, normal rainfall is sufficient to keep the PV module glass 
surface  clean under  most  weather conditions.  If  dirt build-up 
becomes excessive, use only a soft, damp cloth and water to 
clean  the  glass.  If  cleaning  the  back  of  the  PV  module  is 
required,  take  utmost  care  not  to  damage  the  backside 
materials. In order to ensure the operation of the system, check 
the  connection of  wiring and  the state  of  the jacket  of  wires 
occasionally. 
The PV modules is equipped with anti-reflective coating glass, 
do  not touch  the  glass since  fingerprints  or  stains will  easily 
mark.  If  dirt  build-up  becomes  excessive,  clean  the  glass 
surface with water only. 
 Bypass Diode 
(Built-in Junction Box) 
 Bypass Diode 
(Built-in Junction Box) 






