Configurable functions
4.10 Sender test
T
he C4000 sender has a test input on pin 3 for checking the sender and the related re-
ceiver. During the test, the sender no longer emits light beams. Thus, it simulates — for the
receiver — an interruption of the protective field.
During the test the sender indicates .
The test is successful, if the C4000 receiver switches to red, i.e. the output signal
switching devices (OSSDs) are deactivated. In a cascade this only applies for the host.
C4000-Sender and receiver are self-testing and do not require any external sender test.
You can deactivate the sender test with the aid of the CDS, if the test is not required for
the current application.
To be able to perform a sender test …
the option Enable sender test must be active. This is the condition as supplied.
a means of controlling the test input must be available.
Device symbol C4000 Host (sender), context menu Configuration draft, Edit, option
Enable sender test.
If you do not connect the test input, then you must deactivate the Sender test function
with the aid of the CDS. Otherwise the safety light curtain will be permanently switched to
red.
The electrical connection at the test input is described in chapter 6.12 “Test input (sender
test)” on page 62.