AF-S50CX AF-S55CX AF-S60CX SERVICE MANUAL S3207AFS06CX/ AIR CONDITIONER AF-S50CX AF-S55CX MODELS AF-S60CX In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used. TABLE OF CONTENTS Page SPECIFICATIONS ................................................................................................................................................ 2 EXTERNAL DIMENSIONS .
AF-S50CX AF-S55CX AF-S60CX SPECIFICATIONS Models Cooling capacity Moisture removal ELECTRICAL DATA Phase Rared frequency Rated voltage Rated current Rated input Power factor EER BTU/h Pints/h AF-S50CX, AF-S55CX 5000 1.2 AF-S60CX 6000 1.5 Hz Volts Amps Watts % BTU/Wh Single 60 115 4.2 455 94 11.0 5.2 545 91 11.0 (Hermetically sealed rotary type) 39R121AA-C4P, 390W 39R141AA-04P, 460W COMPRESSOR Type Model, Motor output REFRIGERANT SYSTEM Evaporator Condenser Control O.D. x I.D.
AF-S50CX AF-S55CX AF-S60CX ELECTRICAL PARTS Models Running capacitor Fan capacitor Thermistor Fan motor AF-S50CX, AF-S55CX 250V-35µF 250V-6µF 15kΩ at 78˚F OBM-2016K1 AF-S60CX 250V-25µF (MLA998) Overload relay B210-130-241A B200-130-141E WIRING DIAGRAM POWER SUPPLY CORD 115V 60Hz NON RIBBED GR WIRE COLOR BK : BLACK BL : BLUE RE : RED WH : WHITE GR : GREEN GY : GRAY OR : ORANGE 3A 125V IN FU1 CONTROL BOARD UNIT MRY OUT BK NR OVERLOAD PROTECTOR COMPRESSOR C MOTOR RIBBED RUNNING R CAPACITOR 250V
AF-S50CX AF-S55CX AF-S60CX EXTERNAL DIMENSIONS. 17-23/32" 13-5/8" 4-1/8" Fig.
AF-S50CX AF-S55CX AF-S60CX HOW TO OPERATE PARTS NAMES UNIT 5 4 3 6 7 8 9 10 2 1 1Front Cabinet 2Air Inlet (Indoor Side) 3Horizontal Louvers 4Vertical Louvers 5Air Outlet (Indoor Side) 6Control Panel 7Rear Cabinet 8Air Inlet (Outdoor side) 9Filter (Pull the filter handle to the right to remove.
AF-S50CX AF-S55CX AF-S60CX COOLING OPERATION POWER indicator SELECTOR indicator F 2 To turn off the unit, touch POWER ON/OFF pad again. POWER ON/OFF hr COOL / FAN 1 Touch POWER ON/OFF pad. • The unit is preset at 74°F and HIGH COOL. This will show in the display when the power is first turned on. • POWER indicator and SELECTOR indicator (COOL) will light. TEMP TIMER SELECTOR ON/OFF ENERGY SAVER • POWER indicator and SELECTOR indicator will go off.
AF-S50CX AF-S55CX AF-S60CX TO CHANGE FAN SPEED AND OPERATION MODE SELECTOR indicator During operation F POWER ON/OFF hr COOL / FAN Touch SELECTOR pad and select the operation mode and fan speed. • SELECTOR indicator and display will light in order as you touch. TEMP TIMER SELECTOR ON/OFF ENERGY SAVER HIGH COOL MED COOL LOW COOL LOW FAN MED FAN HIGH FAN SELECTOR pad NOTES ON OPERATION MODE: MODE SELECTOR DISPLAY HIGH COOL COOL Cooling operation with high fan speed.
AF-S50CX AF-S55CX AF-S60CX ENERGY SAVER During normal operation, the thermostat automatically controls cooling and the fan runs continuously. When the ENERGY SAVER is selected, the thermostat automatically controls cooling and the fan automatically stops when the compressor is not operating. (Fan will stop 30 seconds after the compressor stops. After the fan stops, the fan is programmed to rotate for approx. 2 minutes to detect room temperature. This will occur within a 20 min time span.
AF-S50CX AF-S55CX AF-S60CX ON TIMER OPERATION • This unit has a built-in timer that can be programmed to start the unit up to 12 hours in advance. You can set the timer to start in increments of 30 minutes (0.5 hours) up to 9.5 hours in advance of the start time, or in 1 hour increments from 10 to 12 hours in advance of the start time. • The unit will start automatically according to your setting.
AF-S50CX AF-S55CX AF-S60CX OFF TIMER OPERATION • This unit has a built-in timer that can be programmed to shut the unit off up to 12 hours in advance. You can set the timer to stop in increments of 30 minutes (0.5 hours) up to 9.5 hours in advance of the stop time, or in 1 hour increments from 10 to 12 hours in advance of the stop time. • The unit will stop automatically according to your setting.
AF-S50CX AF-S55CX AF-S60CX USING THE REMOTE CONTROL INSTALLING BATTERIES Use two size-AAA (R03) batteries. 1 2 Remove the battery compartment cover. 3 Replace the cover. Insert the batteries in the compartment, making sure the and polarities are properly aligned. Battery compartment cover NOTES: • The battery life is approximately one year with normal use. • When you replace the batteries, always use two new ones of the same type.
AF-S50CX AF-S55CX AF-S60CX OPERATING WITH THE REMOTE CONTROL TRANSMITTER POWER ON/OFF POWER ON/OFF button Push to start or stop the operation. TEMP. TEMP. TEMP. TEMP. ---Raise ---Lower temp. setting 1°F at a time. temp. setting 1°F at a time. SELECTOR HIGH COOL SELECTOR button SET TIMER/OFF MED COOL Push to change fan speed and operation mode. Fan speed and operation mode selections are shown to the right.
AF-S50CX AF-S55CX AF-S60CX INSTALLATION INSTRUCTIONS ACCESSORIES 1 No. Accessories Q'ty 1 Right closure assembly 1 2 Left closure assembly 1 3 Window sash foam seal 1 4 Window sash foam seal (adhesive type) 1 5 Bottom gasket 1 6 Screws (L=1", 25.4mm) 7 13 7 Screws (L= /32", 10mm) 6 8 Base pan angle 2 9 Remote control 1 10 Battery 2 11 Remote control hook 1 2 3 4 5 6 7 6 7 8 2 9 11 10 2 SUGGESTED TOOLS 1. Screw driver (medium size Phillips) 2.
AF-S50CX AF-S55CX AF-S60CX INSTALLATION WARNING: Make sure the unit is turned off and unplugged before working. 1 Sash Cut the window sash foam seal (adhesive type) to the proper length and attach it to the underside of the window sash. Window sash foam seal (adhesive type) Jamb Sill 2 3 Insert the right closure assembly and the left closure assembly into the top angle and the bottom channels. Secure the right and left closure to the cabinet with six of the provided screws.
AF-S50CX AF-S55CX AF-S60CX 5 Closure assembly (Left) Insert the closure assemblies on both sides into the rails of the jamb. Jamb (Left) Indoor side Closure assembly (Left) Indoor side 1/2 inches (13mm) Sill Stool 6 Loosen screws on both sides of the cabinet, then hang the base pan angle on and secure the screws again. 7 Secure the base pan angle to the sill by using the hole of the front side on the angle with one screw. (L=1", 25.
AF-S50CX AF-S55CX AF-S60CX DISASSEMBLING PROCEDURE CAUTION: DISCONNECT THE ROOM AIR CONDITIONER FROM THE POWER SUPPLY BEFORE ANY SERVICE 1. Unscrew the 2 screws holding the front panel on each side. 2. Remove the front panel by pulling the front panel at the lower corner toward you about one inch. Next lift up and pull it toward you. 5. Remove the control panel. 6. Unscrew the 5 screws. 3 screws are holding the control box at the top and right side. 1 screw is holding the power supply cord.
AF-S50CX AF-S55CX AF-S60CX 9. Cut the wire fixing band, slide the control box rightward and remove. SLID E 13. Unscrew the 3 screws holding the condenser shround. And remove the condenser shround. 10. Unfasten the one nut at the top of the compressor holding the terminal cover. Then remove the wiring connector of the compressor cord. 14. Unscrew the 5 screws. 2 screws are holding the evaporator on each side. 3 screws are holding the bulkhead to the base pan on each side and back side. 11.
AF-S50CX AF-S55CX AF-S60CX 17. Unscrew the 1 screw holding the centrifugal fan. 18. Remove the caseing. 19. Unscrew the 4 screws holding fan motor.
AF-S50CX AF-S55CX AF-S60CX DISASSEMBLING THE CONTROL BOX 1. Unscrew the 2 screws holding the control box cover. CAUTION: DISCHARGE THE FAN MOTOR CAPACITOR AND RUNNING CAPACITOR BEFORE TOUCHING THOSE CAPACITORS OR OTHER COMPONENTS OR WIRING. 5. Unscrew the 1 power supply cord grounding screw. Unscrew the earth screw. Unscrew the 1 screw holding the capacitor clamp. 6. Detach each connector by using long-noise pliers. 2. Unscrew the 3 screws holding the printed wiring board. 7.
AF-S50CX AF-S55CX AF-S60CX HOW TO REPAIR REFRIGERATION Before sealed system work can be preformed a refrigerant recovery EPA and LOCALLY approved certification is required, additionally, EPA and LOCALLY approved refrigerant recovery equipment is required. SEALED SYSTEM REPAIR Sealed system repairs should be properly diagnosed before entering into a repair of the system.
AF-S50CX AF-S55CX AF-S60CX PROPER FLUXING Flux is necessary when using silver solder; it is not required when using silfos on copper to copper joints. To do a good job the flux should cover the tube surface completely. Be careful not to introduce any flux inside the tubing. Fluxing should be done after the tubing is mated together and just before brazing is done. Do not allow it to dry out. When brazing, the flux should become entirely liquid and clear, like water.
AF-S50CX AF-S55CX AF-S60CX Type of evacuation methods 1. Piston Type Compressor No good. System parts must be above 110˚F. 2. Rotary Vacuum Pump Disavantages. Low CFMC. 4 oil gets dirty. 3. Single State Vacuum Pump will not clean oil. Oil must be changed often. DIAL-CHARGE CHARGING CYLINDER ELECTRIC VACUUM GAUGE LOW SIDE GAUGE TO RELATED SERVICE VALVE OR PROCESS TUBES OF THE UNIT. 4. Two Stage Vacuum Pump will reach 50 microns. First stage is below atmospheric pressure.
AF-S50CX AF-S55CX AF-S60CX ELECTRICAL COMPONENT TEST RUNNING CAPACITOR AND FAN CAPACITOR CAUTION: DISCHARGE THE RUNNING CAPACITOR AND FAN CAPACITOR BEFORE TOUCHING CAPACITOR OR WIRING. (1) Discharge capacitor by shorting terminals. (2) Take the wires off the capacitor terminals. (3) Set the selector switch of a volt-ohm-meter (or a tester) on the resistance range. (4) Connect the probes to the capacitor terminals and watch the indicator swing. The indicator does not swing at all ..... Open.
AF-S50CX AF-S55CX AF-S60CX MICROCOMPUTER CONTROL SYSTEM 1. Temperature control characteristic 1-1 COOL operation In the “COOL” mode, the thermostat circuit is controlled by two thermostat lines (C1, C2). 3. Fan speed Fan speeds are given by the fan motor, “H”, “M” and “L”, which are available in the following operation mode. Room temperature (°F) Table Y-1 86 C1 84 C2 Fan motor H M L H M L 64 4. 12-hours timer 62 64 Preset temperature (°F) ("THERMO" switch) 86 Figure Y-1 2.
AF-S50CX AF-S55CX AF-S60CX 6. Safety start When you turn the air conditioner OFF and restart again soon, wait at least 3 minutes before the cooling operation starts. 7. Test mode Keep pushing both buttons “POWER ON/OFF” and “ " ” and supply the power, the system will go to the test mode. In this mode, the output operation is switched by pushing buttons. Normal outputs are shown in Table Y-2. Table Y-2 For selfdiagnosis check mode No.
BK BK BL BK M CONNECTOR WHITE ORANGE RED GRAY GRAY R BL FAN MOTOR A H M L C S 5 3 1 6 7 RY1 CNR1 RY2 CNR2 RY3 CNR3 3A 125V YELLOW 4 3 2 1 CN1 12V IF NOT SPECIFIED 1SS133T-72 (DIODE) IF NOT SPECIFIED 50V 1000pF (CAPACITOR) : INDICATED POSITION IS FUNCTION TEST POINT RY3 RY2 RY1 MRY 250V 0.
AF-S50CX AF-S55CX AF-S60CX DPWBFA244JBKZ (AF-S55CX) DPWBFA278JBKZ QPWBFB438JBZZ (AF-S55CX) QPWBFB475JBZZ R15 BCN2 DPWBFA278JBKZ DPWBFA244JBKZ (AF-S55CX) QPWBFB475JBZZ QPWBFB438JBZZ (AF-S55CX) Printed Wiring Board 27
AF-S50CX AF-S55CX AF-S60CX TROUBLESHOOTING GUIDE No cooling (Operation not at all.) Measure the power supply voltage at receptacle. under 100V 120V(over 100V) The house fuse or circuit breaker open ? not open. open Is it proper current capacity of the house fuse or the circuit breaker ? Ask the power supply company for check. Change the house fuse and the circuit breaker turn on.
AF-S50CX AF-S55CX AF-S60CX No cooling (Fan operate but the compressor doesn't operate.) Measure the power supply voltage at receptacle. under 100V Ask the power supply 120V(over 100V) company for check. insufficient Is it sufficient current capacity of power equipment ? Ask the power supply Is it small wiring for power company for check. supply equipment ? sufficient Measure the current in compressor circuit. current Check the overload relay. no current imperfect contact Change the overload relay.
AF-S50CX AF-S55CX AF-S60CX No cooling (The compressor operate but the fan motor doesn't operate) crack at the solder part Check BNC1 on PWB ass'y Repair with over solder. disconnecting the connector Connect the connector properly. OK Check the fan motor capacitor. NG OK Measure the resistance of compressor coil. OK Is the fan locked ? Change the fan motor capacitor NG Change the fan motor. locked Is the fan touched to another parts ? touch Change fan or another parts, or adjust.
AF-S50CX AF-S55CX AF-S60CX Insufficient cooling(Both compressor and compressor operate) Check the temperature setting. OK too high Set the lower temperature. dirty Check the air filter. not dirty Clean the air filter. Is there high heat source or any object restricting heat radiation near the unit. there is Remove the high heat source or stop. there isn't Check doors and windows. close Check the outdoor and indoor heat exchanger. open Doors and windows must be kept closed.
AF-S50CX AF-S55CX AF-S60CX Excessive vibration or Abnormal noise At fan only mode, Excessive vibration or Abnormal noise YES Check the air filter dirty NO not dirty Check rotating direction of centrifugal fan.(to clockwise) OK Clean the air filter. NG Check the fan motor connector. OK Measure the resistance of fan motor coil. OK Is the fan deformed or broken. OK Is loosened screw and nut fixing fan ? OK deform or broken Change the fan loosened Tighten up.
AF-S50CX AF-S55CX AF-S60CX COOLING LOAD ESTIMATE FORM INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE FORM FOR ROOM AIR CONDITIONERS (AHAM PUB. NO. RAC-1) A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations which do not require specific conditions of inside temperature and humidity. B. The form is based on an outside design temperature of 95˚F dry bulb and 75˚F wet bulb.
AF-S50CX AF-S55CX AF-S60CX BTU/Hr (Quantity x Factor) FACTORS HEAT GAIN FROM QUANTITY DAY No Shades 1. WINDOWS: Heat gain from sun. Northeast Southeast South Southwest Southeast West Northwest North Inside Shades Outside Shades 20 25 20 20 30 45 35 0 (Area a Factor) Use only the largest load Use only only 60 25 80 40 75 30 75 35 110 45 sq ft 150 65 sq ft sq ft 120 50 sq ft 0 0 These factors are for single glass only. For glass block, multiply the above factors by 0.
AF-S50CX AF-S55CX AF-S60CX RUNNING CONDITION Note: 1. Select mode of the Running Condition of a Room Air Conditioner. SELECTOR .................................................................................................... HIGH COOL THERMOSTAT .............................................................................................. 64˚F 2. Data of Performance Curve is measured between 40%RH and 70%RH.
AF-S50CX AF-S55CX AF-S60CX PACKING AND ACCESSORIES TOP PAD ASSEMBLY (DPADBA004JBFZ) Top pad L Top pad R 4 3 6 5 5 6 Packing case SPAKCA996JBEZ: AF-S50CX SPAKCB050JBEZ: AF-S55CX SPAKCA997JBEZ: AF-S60CX Front side "Front side" mark Accessories Operation manual Window sash foam seal Window sash seal Bottom gasket Screws Base pan angle Right closure assembly Left closure assembly Remote control Battery Remote control hook 2 Protect (SSAKHA009JBEZ) Enegry card TLAB-C213JBEZ: AF-S50CX TLAB-C270JBEZ: AF
AF-S50CX AF-S55CX AF-S60CX REPLACEMENT PARTS LIST REF. NO. PART NO.
AF-S50CX AF-S55CX AF-S60CX REF. NO. PART NO.
AF-S50CX AF-S55CX AF-S60CX REF. NO. PART NO.
AF-S50CX AF-S55CX AF-S60CX 1 2 3 4 5 6 CABINET PARTS 4-19 A A 6-4 4-10 4-9 4-16 4-3 4-4 4-11 4-17 6-9 1-3 4-12 4-2 4-8 1-4 4-5 B 4-14 4-1 B 4-6 6-9 6-11 4-7 4-18 4-15 6-5 4-13 6-4 6-13 1-2 C C 6-10 6-11 6-5 6-1 1-34 1-8 1-9 1-10 1-11 1-12 D 6-4 6-1 1-26 5-3 1-30 1-7 6-4 D 5-1 1-32 1-26 5-2 1-24 1-13 1-25 E 5-4 5-6 [AF-S55CX only] 6-3 E 2-4 1-35 5-5 1-14 1-21 F 1-17 6-8 1-19 F 1-16 1-18 1-22 6-4 1-20 6-2 1-29 1-15 6-3 6-3 G 6-4 G
AF-S50CX AF-S55CX AF-S60CX 1 2 3 4 5 6 CONTROL BOX PARTS A A 1-6 B B 1-5 6-7 2-17 2-10 C C 2-12 6-12 6-7 6-6 2-11 D D 2-7 6-4 2-16 2-8 2-3 2-10 2-5 E 6-5 2-2 6-5 E 2-4 2-6 2-13 6-6 F F 2-14 2-9 2-1 6-4 G G 6-6 H H 1 2 3 4 41 5 6
AF-S50CX AF-S55CX AF-S60CX 1 2 3 4 5 6 CYCLE PARTS A A 6-14 3-13 3-12 B B 3-11 3-10 3-9 2-15 3-4 C C 3-17 6-15 3-3 3-8 D D 3-1 6-3 3-15 [AF-S50CX/S55CX, only] 3-5 3-6 3-14 [AF-S50CX/S55CX, only] 3-7 E E 3-18 3-16 6-15 6-5 3-2 F F G G H H 1 2 3 4 42 5 6
AF-S50CX AF-S55CX AF-S60CX 43
AF-S50CX AF-S55CX AF-S60CX COPYRIGHT © 2002 BY SHARP CORPORATION ALL RIGHTS RESERVED. No part of this publication may be reproduced, stored in retrieval systems, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without prior written permission of the publisher. 44 ’02 SHARP CORP. (3S0.85E) Printed in U.S.A.