Service manual

7
GB
7
Para
Cond
Range
Description
Dim
FD1-11
SL
-50 … SH
Minimum limit for ‘SP’ setting
°C
1
SH
SL … 90°
Maximum limit for ‘SP’ setting
°C
3
SP
SL … SH
Temperature set point to be achieved
°C
1.5
CH
RF HE
Refrigeration or Heating control mode
Flag
RF
HY
1 … 9.9°
Off/On thermostat differential
°K
3
CR
0 … 30min
Compressor rest time
Min
2
C1
0 … 30min
Thermostat run times with faulty T1
probe (‘C1’ = 0 output with faulty T1 will
always be off).
Min
6
C2
0 … 30min
Thermostat off time with faulty T1 probe
(‘C2’ = ‘0’ & ‘C1’ => ‘0’output with
faulty T1 will always be on.)
Min
4
CS
0 … 30min
Compressor stop delay after door has
been opened (only if ‘DS’ – ‘1’)
Min
1
DM
Defrost start mode:
Func.
TM
NO
Defrost is disabled (the following
parameter will be ‘FM’)
TM
Regular time defrost
FR
Defrost time elapses only in condition of
frost accumulation
DB
‘DM’ = ‘TM’ or ‘FR’
0 … 90 Hrs
Time interval between defrosts
Hrs.
6
DF
Defrost timer clock:
Flag
YS
YS
Following mains interruption, timer
resumes count
NO
Following mains interruption, timer
restarts from zero
DL
-50 … 90°
Defrost end temperature (only if ‘T2’ =
‘1’)
°C
15
DT
1 … -0min
Maximum defrost duration
Min
20
DY
Defrost type:
Func.
OF
OF
Timed off cycle defrost (compressor and
heater off)
EL
Electric heater defrost (compressor off,
heater on).
GS
Hot gas defrost (compressor and heater
on)
DS
Defrost synchronisation:
Func.
HI
OF
No synchronisation (defrost occurs
immediately when scheduled).
LO
Defrost waits until T1 = lowest part of
cycle (when compressor would normally
‘cut-off’).
HI
Defrost waits until T1 = highest part of
cycle (when compressor would normally
‘cut-in’).
ST
0 … 30min
Defrost synchronisation time out when
‘DS’ = ‘LO’ to provide maximum time
defrost can be deferred.
Min
5
DP
0 … 90sec
Evaporator pump down. Timed pause at
start of defrost
Sec
0
DN
0 … 30min
Drain down period
Min
1