Installation Guide
SPECIFICATIONS
OXYGEN BARRIER PEX INSTALLATION SUGGESTIONS
Available Sizes: 1" FNPT Inlets, 1/2"-3/4" SharkBite Loop Connections
Maximum Operating Pressure with Installed Flow Meters: 87 psi (6 bar)
Flow Meter Precision: +/- 10%
Maximum Working Temperature: 158°F (70°C)
Maximum Admissible Percentage of Glycol: 30%
Flow Rate (maximum per loop): 2 GPM (7.5 LPM)
Outlets: 3–13 Loops
Outlet Port Spacing: 1.97" (50mm)
•  It is not recommended to put a joint in concrete.
•  Pipe spacing is typically 12" on center for concrete slabs, and 8" on center between floor joists.
•  Use SharkBite Foam Insulation Installation Clips, Wire Mesh Installation Clips, or Subfloor Staples to secure the 
PEX during installation.
•  SharkBite 1/2" PEX has a 5" minimum bend radius.
•  Pressure test the system with air at 80 psi prior to pouring concrete.
•  Ensure that the loop lengths are specified appropriately to avoid excess heat loss. In most systems, the 
maximum length per loop should be 250'.
•  Protect the tubing with non-metallic sleeves when entering or exiting the concrete slab.