SPECIFICATIONS
OXYGEN BARRIER PEX INSTALLATION SUGGESTIONS
Available Sizes: 1" FNPT Inlets, 1/2"-3/4" SharkBite Loop Connections
Maximum Operating Pressure with Installed Flow Meters: 87 psi (6 bar)
Flow Meter Precision: +/- 10%
Maximum Working Temperature: 158°F (70°C)
Maximum Admissible Percentage of Glycol: 30%
Flow Rate (maximum per loop): 2 GPM (7.5 LPM)
Outlets: 3–13 Loops
Outlet Port Spacing: 1.97" (50mm)
It is not recommended to put a joint in concrete.
Pipe spacing is typically 12" on center for concrete slabs, and 8" on center between floor joists.
Use SharkBite Foam Insulation Installation Clips, Wire Mesh Installation Clips, or Subfloor Staples to secure the
PEX during installation.
SharkBite 1/2" PEX has a 5" minimum bend radius.
Pressure test the system with air at 80 psi prior to pouring concrete.
Ensure that the loop lengths are specified appropriately to avoid excess heat loss. In most systems, the
maximum length per loop should be 250'.
Protect the tubing with non-metallic sleeves when entering or exiting the concrete slab.