Specifications

Description
1
Format Range
6
Units or
Resolution Comments
#
Reg
Modbus Address
Hex Decimal
Notes
1
2
3
4
5
6
7
8
9
10
11
12
curren
t
FS = CT numerator * CT multiplie
r
voltag
e
FS = PT numerator * PT multiplie
powe
r
FS = CT numerator * CT multiplier * PT numerator * PT multiplier * 3 [ * SQRT(3) for delta hooku
frequenc
y
FS = 60 (or 50
)
p
ower facto
r
FS = 1.
0
percentag
e
FS = 100.
0
angle FS = 180.0
13
14
If the password is incorrect, a valid response is returned but the command is not executed. Use 5555 for the password if passwords are disabled in the programmable settings.
Data Formats
Writing this register causes data to be saved permanently in EEPROM. If there is an error while saving, a slave device failure exception is returned and programmable settings mode automatically
terminates via reset.
32-bit IEEE floating point number spanning 2 registers. The lower-addressed register is the high order half (i.e., contains the exponent).
All registers not explicitly listed in the table read as 0. Writes to these registers will be accepted but won't actually change the register (since it doesn't exist).
Meter Data Section items read as 0 until first readings are available or if the meter is not in operating mode. Writes to these registers will be accepted but won't actually change the register.
Register valid only in programmable settings update mode. In other modes these registers read as 0 and return an illegal data address exception if a write is attempted.
Not applicable to Shark 100, V-Switch 1, 2, or 3
M denotes a 1,000,000 multiplier.
Meter command registers always read as 0. They may be written only when the meter is in a suitable mode. The registers return an illegal data address exception if a write is attempted in an incorrect
mode.
SINT16 / UINT16 16-bit signed / unsigned integer.
End of Ma
p
Entities to be monitored against limits are identified by Modbus address. Entities occupying multiple Modbus registers, such as floating point values, are identified by the lower register addrress. If any
of the 8 limits is unused, set its identifier to zero. If the indicated Modbus re
g
ister is not used or is a non-sensical entit
y
for limits, it will behave as an unused
l
ASCII ASCII characters packed 2 per register in high, low order and without any termination characters. For example, "Shark100" would be 4 registers containing 0x5378, 0x6172, 0x6B31,
0x3030
.
There are 2 setpoints per limit, one above and one below the expected range of values. LM1 is the "too high" limit, LM2 is "too low". The entity goes "out of limit" on LM1 when its value is greater than
the setpoint. It remains "out of limit" until the value drops below the in threshold. LM2 works similarly, in the opposite direction. If limits in only one direction are of interest, set the in threshold on the
"wrong" side of the setpoint. Limits are specified as % of full scale, where full scale is automatically set appropriately for the entity being monitored:
Energy registers should be reset after a format change.
Reset commands make no sense if the meter state is LIMP. An illegal function exception will be returned.
SINT32 / UINT32
FLOAT
32-bit signed / unsigned integer spanning 2 registers. The lower-addressed register is the high order half.
THD not available shows 65535 (=0xFFFF) in all THD and harmonic magnitude registers for the channel when V-switch=4. THD may be unavailable due to low V or I amplitude, or delta hookup (V
only).
All 3 voltage angles are measured for Wye and Delta hookups. For 2.5 Element, Vac is measured and Vab & Vbc are calculated. If a voltage phase is missing, the two voltage angles in which it
participates are set to zero. A and C phase current angles are measured for all hookups. B phase current angle is measured for Wye and is zero for other hookups. If a voltage phase is missing, its
current angle is zero.
e
Electro Industries/GaugeTech
Doc# E145701 MM-8