Specifications

e
Electro Industries/GaugeTech
Doc #: E145701 6-2
Q
Enter Button: Press and release to enter one of four Display Modes
Operating Mode (Default),
Reset Mode (ENTER once, then Down)
Settings Mode (ENTER twice, then Down) and
Configuration Mode (ENTER three times, then Down)
Q
Menu Button: Press and release to navigate Config Menu, return to Main Menu
Q
Right Button: Operating Mode - Max, Min, %THD, Del kW, Net kW, Total kW
Reset Mode - Yes, No
Settings Mode - On, Off, Settings
Config Mode - Password Digits, Available Values, Digits
Q
Down Button: Scroll DOWN through Mode menus
Q
Use Buttons in Modes of Operation:
Operating Mode (default): View Parameter Values
Reset Mode: Reset Stored Max and Min Values
Settings Mode: View Meter Setting Parameters and Change Scroll Setting
Configuration Mode: Change Meter Configuration (Can be Password Protected)
NOTE: The above is a brief overview of the use of the Buttons. For Programming, refer to Chapter 7.
For complete Navigation Maps, refer to Appendix A of this manual.
6.2:
%
of
Load
Bar
Q
The 10-segment LED bargraph at the bottom of the Shark display provides a graphic representation
of Amps. The segments light according to the load in the %Load Segment Table below.
When the Load is over 120% of Full Load, all segments flash “On” (1.5 secs) and “Off” (0.5 secs).
Segments Load >= % Full Load
none no load
11%
1 - 2 15%
1 - 3 30%
1 - 4 45%
1 - 5 60%
1 - 6 72%
1 - 7 84%
1 - 8 96%
1 - 9 108%
% Load Segment Table
1 - 10 120%
All Blink >120%