Specifications
e
Electro Industries/GaugeTech
Doc #: E145701 2-6
2.3:
Compliance
• IEC 687 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
• ANSI (IEEE) C37.90.1 Surge Withstand
• ANSI C62.41 (Burst)
• IEC1000-4-2: ESD
• IEC1000-4-3: Radiated Immunity
• IEC1000-4-4: Fast Transient
• IEC1000-4-5: Surge Immunity
2.4:
Accuracy
Measured Parameters
Accuracy % of
Reading*
Display Range
Voltage L-N 0.1% 0-9999 V or kV Autoscale
0.1% 0-9999 V or kV AutoscaleVoltage L-L
0.1% 0-9999 A or kA Autoscale
+/- Watts 0.2% 0-9999 Watts, kWatts, MWatts
+/- Wh 0.2% 5 to 8 Digits Programmable
+/- VARs 0.2% 0-9999 VARs, kVARs, MVARs
+/- VARh 0.2% 5 to 8 Digits Programmable
VA 0.2% 0-9999 VA, kVA, MVA
VAh 0.2% 5 to 8 Digits Programmable
Meter Accuracy by Measured Parameters
0.2%PF +/- 0.5 to 1.0
Frequency +/- 0.01 Hz 45 to 65 Hz
% THD 2.0% F.S. 0 to 100%
% Load Bar 1 - 120% 10 Segment Resolution Scalable
* Accuracy stated for 5 amp secondary WYE or Delta connections. For 1 amp secondary
or 2.5 element connections, add 0.1% of Full Scale + 1 digit to accuracy specification.
Current Phase
2.0% F.S. 0-9999 A or kA AutoscaleCurrent Neutral (Calculated)