Specifications

e
Electro Industries/GaugeTech
Doc #: E145701 2-4
2.1.5:
Utility
Peak
Demand
The Shark® 100 meter provides user-configured Block (Fixed) Window or Rolling Window
Demand. This feature allows you to set up a Customized Demand Profile. Block Window Demand
is demand used over a user-configured demand period (usually 5, 15 or 30 minutes). Rolling
Window Demand is a fixed window demand that moves for a user-specified subinterval period. For
example, a 15-minute Demand using 3 subintervals and providing a new demand reading every 5
minutes, based on the last 15 minutes.
Utility Demand Features can be used to calculate kW, kVAR, kVA and PF readings. All other
parameters offer Max and Min capability over the user-selectable averaging period. Voltage
provides an Instantaneous Max and Min reading which displays the highest surge and lowest sag
seen by the meter
2.2:
Specifications
Q
Power Supply
Range: D2 Option: Universal, (90 to 265) VAC @50/60Hz or (100 to
370) VDC
D Option: (18-60) VDC
Power Consumption: 5 VA, 3.5W
Q
Voltage Inputs (Measurement Category III)
Range: Universal, Auto-ranging up to 416Vac L-N, 721Vac L-L
Supported hookups: 3 Element Wye, 2.5 Element Wye, 2 Element Delta, 4 Wire
Delta
Input Impedance: 1M Ohm/Phase
Burden: 0.0144VA/Phase at 120 Volts
Pickup Voltage: 10Vac
Connection: Screw terminal (Diagram 4.4)
Max Input Wire Gauge: AWG#12 / 2.5mm2
Fault Withstand: Meets IEEE C37.90.1
Reading: Programmable Full Scale to any PT Ratio
Q
Current Inputs
Class 10: 5A Nominal, 10A Maximum
Class 2: 1A Nominal, 2A Maximum
Burden: 0.005VA Per Phase Max at 11 Amps
Pickup Current: 0.1% of Nominal
Connections: O or U Lug Electrical Connection (Diagram 4.1)
Pass-through Wire, 0.177" / 4.5mm Maximum Diameter
(Diagram 4.2)
Quick Connect, 0.25" Male Tab (Diagram 4.3)
Fault Withstand: 100A/10sec., 300A/3sec., 500A/1sec.
Reading: Programmable Full Scale to any CT Ratio