Specifications
e
Electro Industries/GaugeTech
Doc #: E145701 D-5
• Change to Modbus RTU Protocol ( Point 1 )
Shark meters are capable of changing from DNP Protocol to Modbus RTU Protocol. This
enables the user to update the Device Profile of the meter. This does not change the Protocol
setting. A meter reset brings you back to DNP.
Use of the DIRECT OPERATE - NO ACKNOWLEDGE ( Function 6 ) function will operate
only with the settings of Pulsed ON ( Code = 1 of Control Code Field ) once ( Count = 0x01 )
for ON 1 millisecond and OFF 0 milliseconds.
D.4.1.3:
32-BBit
Binary
Counter
Without
Flag
(
Obj.
20,
Var.
5
)
Counters support the following functions:
Read ( Function 1 )
A READ request for Variation 0 will be responded to with Variation 5.
Counters are used to communicate the following data measured by Shark meters:
Hour Readings
Q
Hour Readings (Points 0 - 4)
* These readings may be cleared by using the Contol Relay Output Block.
Point Readings Unit
0 +W Hour Wh
1 -W Hour Wh
2 +VAR Hour VARh
3 -VAR Hour VARh
4 +VA Hour VAh